subscribe iconSubscribe to this information

Model 9406-270 server specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Use the following specifications to plan for your server. The 7104 expansion unit requires a power cord. Dimensions are shown for model 9406-270 only.

Pictured is model 9406-270. The 7104 expansion unit is available with model 9406-270.

model 9406-270
Table 1. Dimensions
Measurements 9406-270 width 9406-270 with 7104 width 9406-270 depth 9406-270 height
Metric 366 mm 552 mm 728 mm 610 mm
English 14.5 in. 21.9 in. 28.7 in. 24.0 in.
Table 2. Maximum configuration weight
Model 9406-270 Model 9406-270 with 7104
52.7 kg (116 lb) 79.5 kg (175 lb)
Table 3. Electrical Model 9406-270
Power factor 0.95    
Inrush current 41 A Maximum kVA (each has its own power cord) 0.421
Leakage current (maximum) 3.5 mA Rated voltage and frequency3 100-127/200-240 V ac at 50-60 plus or minus 0.5 Hz
Phase 1 Thermal output (maximum) 1365 Btu/hr
Table 4. Electrical 7104 expansion unit
Power factor 0.95    
Inrush current 41 A Maximum kVA (each has its own power cord) 0.368
Leakage current (maximum) 3.5 mA Rated voltage and frequency3 100-127/200-240 V ac at 50-60 plus or minus 0.5 Hz
Phase 1 Thermal output (maximum) 1194 Btu/hr
Table 5. Temperature requirements
Operating Nonoperating
10 - 38°C (50 - 100.4°F) 1 - 60°C (33.8 - 140°F)
Table 6. Environment requirements
Environment Operating Nonoperating
Noncondensing humidity 8 - 80% 8 - 80%
Wet bulb temperature 23°C (73.4 - °F) 27°C (80.6 - °F)
Maximum altitude 3048 m (10 000 ft)  
Table 7. Noise emissions1
Operating Idle
LWAd (Category 2E, General business) 9406-270 only 5.9 bels 5.8 bels
LWAd (Category 2E, General business) 9406-270 with 7104 6.3 bels 6.1 bels
LpAm (1-meter bystander) 9406-270 only 41 dB 40 dB
LpAm (1-meter bystander) 9406-270 with 7104 45 dB 43 dB
Table 8. Service clearances
Measurements Front Back Sides 2 Top 2
Metric 762 mm 762 mm 762 mm 762 mm
English 30 in. 30 in. 30 in. 30 in.
Table 9. Notes
Notes:
  1. For a description of noise emission values, see Acoustics.
  2. Side and top clearances are optional when operating.
  3. The power supplies automatically accept any voltage with the published rated voltage range. If dual power supplies are installed and operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.

Send feedback | Rate this page