Server specifications provide detailed information for
your server, including dimensions, electrical, power, temperature,
environment, and service clearances.
Use the following specifications to plan for your server.
The 7104 expansion unit requires a power cord. Dimensions are shown
for model 9406-270 only.
Pictured is model 9406-270. The 7104
expansion unit is available with model 9406-270.
Table 1. Dimensions Measurements |
9406-270 width |
9406-270 with 7104 width |
9406-270 depth |
9406-270 height |
Metric |
366 mm |
552 mm |
728 mm |
610 mm |
English |
14.5 in. |
21.9 in. |
28.7 in. |
24.0 in. |
Table 2. Maximum configuration
weightModel 9406-270 |
Model 9406-270 with 7104 |
52.7 kg (116 lb) |
79.5 kg (175 lb) |
Table 3. Electrical Model 9406-270 Power factor |
0.95 |
|
|
Inrush current |
41 A |
Maximum kVA (each has its own power
cord) |
0.421 |
Leakage current (maximum) |
3.5 mA |
Rated voltage and frequency3 |
100-127/200-240 V ac at 50-60
plus or minus 0.5 Hz |
Phase |
1 |
Thermal output (maximum) |
1365 Btu/hr |
Table 4. Electrical 7104 expansion
unit Power factor |
0.95 |
|
|
Inrush current |
41 A |
Maximum kVA (each has its own power
cord) |
0.368 |
Leakage current (maximum) |
3.5 mA |
Rated voltage and frequency3 |
100-127/200-240 V ac at 50-60 plus or minus
0.5 Hz |
Phase |
1 |
Thermal output (maximum) |
1194 Btu/hr |
Table 5. Temperature requirements Operating |
Nonoperating |
10 - 38°C (50 - 100.4°F) |
1 - 60°C (33.8 - 140°F) |
Table 6. Environment requirementsEnvironment |
Operating |
Nonoperating |
Noncondensing humidity |
8 - 80% |
8 - 80% |
Wet bulb temperature |
23°C (73.4 - °F) |
27°C (80.6 - °F) |
Maximum altitude |
3048 m (10 000 ft) |
|
Table 7. Noise emissions1 |
Operating |
Idle |
LWAd (Category 2E, General business)
9406-270 only |
5.9 bels |
5.8 bels |
LWAd (Category 2E, General business)
9406-270 with 7104 |
6.3 bels |
6.1 bels |
LpAm (1-meter bystander) 9406-270
only |
41 dB |
40 dB |
LpAm (1-meter bystander) 9406-270
with 7104 |
45 dB |
43 dB |
Table 8. Service clearancesMeasurements |
Front |
Back |
Sides 2 |
Top 2 |
Metric |
762 mm |
762 mm |
762 mm |
762 mm |
English |
30 in. |
30 in. |
30 in. |
30 in. |
Table 9. NotesNotes: - For a description of noise emission values, see Acoustics.
- Side and top clearances are optional when operating.
- The power supplies automatically accept any voltage with the published
rated voltage range. If dual power supplies are installed and operating,
the power supplies draw approximately equal current from the utility
(mains) and provide approximately equal current to the load.
|