5887 expansion unit
Hardware specifications provide detailed information for your expansion unit, including dimensions, electrical, power, temperature, environment, and service clearances.
Weight (with drives installed) | Width | Depth (including front bezel) | Height (with support rails) |
---|---|---|---|
25.4 kg (56.0 lb) | 448.6 mm (17.7 in.) | 530 mm (20.9 in.) | 87.4 mm (3.4 in.) |
Electrical characteristics | Properties |
---|---|
kVA (maximum)1 | 0.32 |
Rated voltage and frequency | 100 - 127 V ac or 200 - 240 V ac at 50 - 60 Hz |
Thermal output (maximum)1 | 1024 Btu/hr |
Power requirements (maximum) | 300 W |
Power factor | 0.94 |
Leakage current (maximum) | 1.2 mA |
Phase | 1 |
1All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296. |
Operating | Nonoperating |
---|---|
10°C - 38°C (50°F - 100.4°F)1 | -40°C - 60°C (-40°F - 140°F) |
1The maximum 38°C (100.4°F) temperature must be derated 1°C (1.8 °F) per 137 m (450 ft) above 1295 m (4250 ft). |
Environment | Operating | Nonoperating | Maximum altitude |
---|---|---|---|
Noncondensing humidity | 20% - 80% (allowable) 40% - 55% (recommended) |
8% - 80% (including condensing) | 2134 m (7000 ft) above sea level |
Wet bulb temperature | 21°C (69.8°F) | 27°C (80.6°F) |
Properties | Operating | Idle |
---|---|---|
LWAd | 6.0 bels | 6.0 bels |
LpAm (1-meter bystander) | 43 dB | 43 dB |
1Single drawer in standard 19-inch rack with 24 hard drives, nominal environmental conditions, and no front or rear doors on rack. For a description of noise emission values, see Acoustics. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296. |
Front | Back | Sides |
---|---|---|
914 mm (36 in.) | 914 mm (36 in.) | 914 mm (36 in.) |
Side and top clearances are optional during operation. |
Safety compliance: This hardware is designed and certified to meet the following safety standards: UL 60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all National Differences