Preventive Service Planning
Abstract
The following document outlines power and cooling requirements for the IBM Storwize V7000.
Content
To aid in power and cooling requirements planning for the Storwize V7000, the following table lists the rating of each power supply unit (PSU) used in the different models of enclosure. The Storwize V7000 models 2076-124 and the 2076-112 use two of the 764W PSUs. The Storwize V7000 models 2076-224 and 2076-212 use two of the 580W PSUs.
|
PSU
|
Input
|
Maximum Power Output
|
Caloric value BTU/hr
|
|
764W
|
100 - 240V
10 - 6A At a frequency of 50 Hz or 60Hz |
764W
|
2607 BTU/hour
|
|
580W
|
100 - 240V
8 - 3A At a frequency of 50 Hz or 60Hz |
580W
|
1980 BTU/hour
|
The power and thermal measurements shown below were obtained in the specific operating environment and under the conditions described below and are presented as an illustration. Measurements obtained in other operating environments may vary and customers should conduct their own testing.
The following measurements were taken whilst using the Storwize V7000 at between 23 and 27 degrees Celsius ambient with a typical workload.
|
Model
|
Configuration
|
Total Power Consumption
|
Calorific Value BTU/hr
|
|
2076-124
|
1 enclosure with 24, Solid State Drives
|
530 W
|
1800 BTU/hour
|
|
2076-324
|
1 enclosure with 24, Solid State Drives
|
560 W
|
1800 BTU/hour
|
|
2076-124
|
1 enclosure with 24, 10k SAS Drives
|
410 W
|
1400 BTU/hour
|
|
2076-224
|
1 enclosure with 24, 10k SAS Drives
|
205 W
|
700 BTU/hour
|
|
2076-324
|
1 enclosure with 24, 10k SAS Drives
|
440 W
|
1500 BTU/hour
|
|
2076-124
|
1 enclosure with 24, 15k SAS Drives
|
430 W
|
1460 BTU/hour
|
|
2076-224
|
1 enclosure with 24, 15k SAS Drives
|
215 W
|
730 BTU/hour
|
|
2076-324
|
1 enclosure with 24, 15k SAS Drives
|
460 W
|
1560 BTU/hour
|
|
2076-112
|
1 enclosure with 12, 7.2k nearline SAS Drives
|
380 W
|
1300 BTU/hour
|
|
2076-212
|
1 enclosure with 12, 7.2k nearline SAS Drives
|
175 W
|
600 BTU/hour
|
|
2076-312
|
1 enclosure with 12, 7.2k nearline SAS Drives
|
410 W
|
1400 BTU/hour
|
Each Storwize V7000 model contains 2 PSUs for redundancy. The Total Power Consumption represents the total of the power drawn across both PSUs.
| Segment | Product | Component | Platform | Version | Edition |
|---|---|---|---|---|---|
| Disk Storage Systems | IBM Storwize V7000 (2076) | 6.4 | IBM Storwize V7000 | 6.1, 6.2, 6.3, 6.4 | |
| Disk Storage Systems | IBM Storwize V7000 Unified (2073) | Not Applicable | Platform Independent | 1.3 |
Rate this page:
Copyright and trademark information
IBM, the IBM logo and ibm.com are trademarks of International Business Machines Corp., registered in many jurisdictions worldwide. Other product and service names might be trademarks of IBM or other companies. A current list of IBM trademarks is available on the Web at "Copyright and trademark information" at www.ibm.com/legal/copytrade.shtml.