Preventive Service Planning
Abstract
The following document outlines power and cooling requirements for the IBM Storwize V7000.
Content
To aid in power and cooling requirements planning for the Storwize V7000, the following table lists the rating of each power supply unit (PSU) used in the different models of enclosure. The Storwize V7000 models 2076-124, 2076-324 and the 2076-112, 2076-312 use two of the 764W PSUs. The Storwize V7000 models 2076-224 and 2076-212 use two of the 580W PSUs. The Storwize V7000 model 2076-524 uses two of the 1200W PSUs. The Storwize V7000 models 2076-24F and 2076-12F use two of the 800W PSUs.
PSU | Input | Maximum Power Output | Caloric value BTU/hr |
1200W | 100 - 240V 12 - 7A At a frequency of 50 Hz or 60Hz | 1200W | 4095 BTU/hour |
800W | 100 - 240V 10 - 6A At a frequency of 50 Hz or 60Hz | 800W | 2730 BTU/hour |
764W | 100 - 240V 10 - 6A At a frequency of 50 Hz or 60Hz | 764W | 2607 BTU/hour |
580W | 100 - 240V 8 - 3A At a frequency of 50 Hz or 60Hz | 580W | 1980 BTU/hour |
The power and thermal measurements shown below were obtained in the specific operating environment and under the conditions described below and are presented as an illustration. Measurements obtained in other operating environments may vary and customers should conduct their own testing.
The power consumption of an enclosure can be read directly using lsenclosurestats command.
The following measurements were taken whilst using the Storwize V7000 at between 23 and 27 degrees Celsius ambient with a typical workload.
Model | Configuration | Total Power Consumption | Calorific Value BTU/hr |
2076-524 | 1 enclosure with 24, Solid State Drives, 2 host adapters, 2 compression accelerators | 452 W | 1542 BTU/hour |
2076-24F | 1 enclosure with 24, Solid State Drives | 151 W | 515 BTU/hour |
2076-124 | 1 enclosure with 24, Solid State Drives | 530 W | 1800 BTU/hour |
2076-324 | 1 enclosure with 24, Solid State Drives | 560 W | 1800 BTU/hour |
2076-524 | 1 enclosure with 24, 10k SAS Drives, 2 host adapters, 2 compression accelerators | 430 W | 1467 BTU/hour |
2076-24F | 1 enclosure with 24, 10k SAS Drives | 175 W | 597 BTU/hour |
2076-124 | 1 enclosure with 24, 10k SAS Drives | 410 W | 1400 BTU/hour |
2076-224 | 1 enclosure with 24, 10k SAS Drives | 205 W | 700 BTU/hour |
2076-324 | 1 enclosure with 24, 10k SAS Drives | 440 W | 1500 BTU/hour |
2076-524 | 1 enclosure with 24, 15k SAS Drives, 2 host adapters, 2 compression accelerators | 471 W | 1607 BTU/hour |
2076-24F | 1 enclosure with 24, 15k SAS Drives | 234 W | 798 BTU/hour |
2076-124 | 1 enclosure with 24, 15k SAS Drives | 430 W | 1460 BTU/hour |
2076-224 | 1 enclosure with 24, 15k SAS Drives | 215 W | 730 BTU/hour |
2076-324 | 1 enclosure with 24, 15k SAS Drives | 460 W | 1560 BTU/hour |
2076-12F | 1 enclosure with 12, 7.2k nearline SAS Drives | 158 W | 539 BTU/hour |
2076-112 | 1 enclosure with 12, 7.2k nearline SAS Drives | 380 W | 1300 BTU/hour |
2076-212 | 1 enclosure with 12, 7.2k nearline SAS Drives | 175 W | 600 BTU/hour |
2076-312 | 1 enclosure with 12, 7.2k nearline SAS Drives | 410 W | 1400 BTU/hour |
Each Storwize V7000 model contains 2 PSUs for redundancy. The Total Power Consumption represents the total of the power drawn across both PSUs.
[{"Product":{"code":"ST3FR7","label":"IBM Storwize V7000"},"Business Unit":{"code":"BU058","label":"IBM Infrastructure w\/TPS"},"Component":"6.4","Platform":[{"code":"","label":"IBM Storwize V7000"}],"Version":"6.1;6.2;6.3;6.4","Edition":"","Line of Business":{"code":"LOB26","label":"Storage"}},{"Product":{"code":"ST3FR7","label":"IBM Storwize V7000"},"Business Unit":{"code":"BU058","label":"IBM Infrastructure w\/TPS"},"Component":"6.4","Platform":[{"code":"","label":"IBM Storwize V7000"}],"Version":"6.1;6.2;6.3;6.4","Edition":"","Line of Business":{"code":"LOB26","label":"Storage"}},{"Product":{"code":"ST5Q4U","label":"IBM Storwize V7000 Unified (2073)"},"Business Unit":{"code":"BU058","label":"IBM Infrastructure w\/TPS"},"Component":"Not Applicable","Platform":[{"code":"PF025","label":"Platform Independent"}],"Version":"1.3","Edition":"","Line of Business":{"code":"","label":""}}]