IBM Support

Power and Cooling Requirements for the IBM Storwize V7000

Preventive Service Planning


Abstract

The following document outlines power and cooling requirements for the IBM Storwize V7000.

Content

To aid in power and cooling requirements planning for the Storwize V7000, the following table lists the rating of each power supply unit (PSU) used in the different models of enclosure. The Storwize V7000 models 2076-124, 2076-324 and the 2076-112, 2076-312 use two of the 764W PSUs. The Storwize V7000 models 2076-224 and 2076-212 use two of the 580W PSUs. The Storwize V7000 model 2076-524 uses two of the 1200W PSUs. The Storwize V7000 models 2076-24F and 2076-12F use two of the 800W PSUs.


PSU
Input
Maximum Power Output
Caloric value BTU/hr
1200W
100 - 240V
12 - 7A
At a frequency of 50 Hz or 60Hz
1200W
4095 BTU/hour
800W
100 - 240V
10 - 6A
At a frequency of 50 Hz or 60Hz
800W
2730 BTU/hour
764W
100 - 240V
10 - 6A
At a frequency of 50 Hz or 60Hz
764W
2607 BTU/hour
580W
100 - 240V
8 - 3A
At a frequency of 50 Hz or 60Hz
580W
1980 BTU/hour


The power and thermal measurements shown below were obtained in the specific operating environment and under the conditions described below and are presented as an illustration. Measurements obtained in other operating environments may vary and customers should conduct their own testing.
The power consumption of an enclosure can be read directly using lsenclosurestats command.

The following measurements were taken whilst using the Storwize V7000 at between 23 and 27 degrees Celsius ambient with a typical workload.


Model
Configuration
Total Power Consumption
Calorific Value BTU/hr
2076-524
1 enclosure with 24, Solid State Drives, 2 host adapters, 2 compression accelerators
452 W
1542 BTU/hour
2076-24F
1 enclosure with 24, Solid State Drives
151 W
515 BTU/hour
2076-124
1 enclosure with 24, Solid State Drives
530 W
1800 BTU/hour
2076-324
1 enclosure with 24, Solid State Drives
560 W
1800 BTU/hour




2076-524
1 enclosure with 24, 10k SAS Drives, 2 host adapters, 2 compression accelerators
430 W
1467 BTU/hour
2076-24F
1 enclosure with 24, 10k SAS Drives
175 W
597 BTU/hour
2076-124
1 enclosure with 24, 10k SAS Drives
410 W
1400 BTU/hour
2076-224
1 enclosure with 24, 10k SAS Drives
205 W
700 BTU/hour
2076-324
1 enclosure with 24, 10k SAS Drives
440 W
1500 BTU/hour




2076-524
1 enclosure with 24, 15k SAS Drives, 2 host adapters, 2 compression accelerators
471 W
1607 BTU/hour
2076-24F
1 enclosure with 24, 15k SAS Drives
234 W
798 BTU/hour
2076-124
1 enclosure with 24, 15k SAS Drives
430 W
1460 BTU/hour
2076-224
1 enclosure with 24, 15k SAS Drives
215 W
730 BTU/hour
2076-324
1 enclosure with 24, 15k SAS Drives
460 W
1560 BTU/hour




2076-12F
1 enclosure with 12, 7.2k nearline SAS Drives
158 W
539 BTU/hour
2076-112
1 enclosure with 12, 7.2k nearline SAS Drives
380 W
1300 BTU/hour
2076-212
1 enclosure with 12, 7.2k nearline SAS Drives
175 W
600 BTU/hour
2076-312
1 enclosure with 12, 7.2k nearline SAS Drives
410 W
1400 BTU/hour



Each Storwize V7000 model contains 2 PSUs for redundancy. The Total Power Consumption represents the total of the power drawn across both PSUs.

[{"Product":{"code":"ST3FR7","label":"IBM Storwize V7000"},"Business Unit":{"code":"BU058","label":"IBM Infrastructure w\/TPS"},"Component":"6.4","Platform":[{"code":"","label":"IBM Storwize V7000"}],"Version":"6.1;6.2;6.3;6.4","Edition":"","Line of Business":{"code":"LOB26","label":"Storage"}},{"Product":{"code":"ST3FR7","label":"IBM Storwize V7000"},"Business Unit":{"code":"BU058","label":"IBM Infrastructure w\/TPS"},"Component":"6.4","Platform":[{"code":"","label":"IBM Storwize V7000"}],"Version":"6.1;6.2;6.3;6.4","Edition":"","Line of Business":{"code":"LOB26","label":"Storage"}},{"Product":{"code":"ST5Q4U","label":"IBM Storwize V7000 Unified (2073)"},"Business Unit":{"code":"BU058","label":"IBM Infrastructure w\/TPS"},"Component":"Not Applicable","Platform":[{"code":"PF025","label":"Platform Independent"}],"Version":"1.3","Edition":"","Line of Business":{"code":"","label":""}}]