7014-T42 IBM Rack Model T42

7014-T42 IBM Rack Model T42

IBM Asia Pacific Sales Manual
Revised:  December 16, 2014.

Table of contents
TOC Link Product life cycle dates TOC Link Publications
TOC Link Abstract TOC Link Features
TOC Link Highlights TOC Link Accessories
TOC Link Description TOC Link Machine elements
TOC Link Models TOC Link Supplies
TOC Link Technical description  

 
Product life cycle dates
Type Model Announced Available Marketing Withdrawn Service Discontinued
7014-T42 2000/05/092000/08/04 - -

Back to topBack to top
 
Abstract

IBM Power Systems and earlier UNIX systems consisting of the IBM System p5, IBM eServer pSeries and IBM RS/6000 product lines provide great value. These innovative systems feature IBM's leading-edge technology and run the top-rated operating systems of AIX, IBM i and Linux. This broad product line ranges from powerful workstations to mission-critical symmetric multiprocessing (SMP) servers for ERP, SCM, CRM, transaction processing, web serving; demanding scientific and technical computing and business intelligence tasks. These platforms provide the power to create change and the flexibility to manage it, with thousands of applications that provide real value.

Model abstract 7014-T42

The IBM 7014 Rack Model T42 is a 2.0 meter rack that will address the special requirements of customers who want a very tall enclosure to house the maximum equipment in the smallest possible floor space. The T42 provides 42 EIA units (42U) of usable space. Because of its height, special shipping and handling procedures may be required in some cases.

The T42 is compatible with the #0553 19-inch rack and compatible with past racks used such as the Model R00/S00 and RS/6000 racks. Features include:


Back to topBack to top
 
Highlights

See Model Highlights.

Model highlights 7014-T42


Back to topBack to top
 
Description

The 2.0 meter 7014-T42 rack has 42 EIA units (42U) of vertical mounting space for 19-inch drawers. An EIA unit is an industry standard for indicating vertical mounting space in a rack, where 1U equals 44.45 mm (1.75 in). This rack meets the Electronics Industries Association EIA-310-D standard. The standard color is black. The racks are also orderable in a white color that matches the some older IBM equipment.

Side Panels and Side To Side Rack Suite Attachment

The rack side panels are optional, and can be quickly installed or removed from the outside of the rack, with no tools required. This design allows a row of racks without side panels to be bolted together in a continuous suite, using the optional side to side rack connecting hardware. When multiple racks are joined in this way, cables can be easily run between racks without having to exit the continuous rack enclosure. A small gap is maintained between the two adjacent racks, which is filled by three matching steel trim pieces that snap into place on the front, top, and rear, between each rack. The trim pieces cover the space between each rack for an enhanced appearance and for additional protection of the equipment inside the racks. Side panels are needed only for the two end racks of the suite. The same removable side panels are used for both the Model T00 and Model T42 racks. On T42 racks, there are additional side covers for the portion of the rack that extends above 1.8 meters.

Front Door and Front Trim Kit

The optional front door has an appearance that is consistent with the S80 and other current RS/6000 Enterprise Systems. The main surface is steel, with a perforated hole pattern that is designed to provide the required ventilation and sufficient visibility of indicator lights for equipment installed inside the rack. Each rack must be ordered with either a front door or a front trim kit (but not both). The front trim kit consists of steel parts that snap into the front of the rack at the left, right, and top edges. They are painted to match the overall rack color and present an attractive appearance that is consistent with the RS/6000 brand image. Because the T42 rack is taller than the T00 rack, the front doors, front trim kits, and side to side rack connecting kits require different sets of features for the two models.

Ruggedized Rack Feature

For enhanced rigidity and stability of the rack, the optional Ruggedized Rack Feature provides additional hardware that reinforces the rack and anchors it to the floor. This hardware is designed primarily for use in locations where earthquakes are a concern. The feature includes a large steel brace that bolts into the rear of the rack. It is hinged on the left side so it can swing out of the way for easy access to the rack drawers when necessary. The Ruggedized Rack Feature also includes hardware for bolting the rack to a concrete floor, and bolt-in steel filler panels for any unoccupied spaces in the rack.

Rear Door Heat Exchanger for 7014-T42

The IBM Rear Door Heat Exchanger is an effective way to assist your AC system in keeping your datacenter cool. It removes heat generated by the systems in the rack before the heat enters the room, allowing your air conditioning unit to handle increasingly dense system deployments. It may also offer a convenient way to handle dangerous "hot spots" in your data center.

Inside the door of the heat exchanger, sealed tubes filled withcirculating chilled water effectively remove up to 55% of the heat generated in a fully populated rack and dissipate it so it is not released into the data center. In fact, the heat exchanger can remove up to 15 kW (approximately 50,000 BTUs/hr) of heat generated by a full server rack, based on total rack output.

The heat exchanger can be easily installed by customers and moved to different 7014-T42 racks to address changing cooling requirements. Its unique design uses standard fittings and couplings and, because there are no moving or electrical parts, helps increase reliability. It can be opened like any rear cover, so serviceability of racks fitted with a heat exchanger is as easy as a standard air cooled rack.

Other Standard Equipment and Optional Features

Each rack is shipped with standard equipment that includes a rear door, front and rear anti-tilt plates, four leveling feet, snap-in filler panels for any unoccupied rack space, and an AC power distribution unit (PDU) mounted inside the rack in an area that is separate from the drawer mounting area. There is room for up to 4 PDU's without using any of the rack's 42U capacity. The rack drawer mounting area is centered relative to the two sides of the rack, which provides ample room to route cables within the frame on both the left and right sides. There are numerous anchor points formed into the frame where cables can be tied down for strain relief.

Feature Availability Matrix

The following feature availability matrix for MT 7014 uses the letter "A" to indicate features that are available and orderable on the specified models. "S" indicates a feature that is supported on the new model during a model conversion; these features will work on the new model, but additional quantities of these features cannot be ordered on the new model; they can only be removed. "N" indicates that the feature is not supported on the new model and must be removed during the model conversion. As additional features are announced, supported, or withdrawn, this list will be updated. Please check with your Marketing Representative for additional information.

        |T| A = AVAILABLE  S = SUPPORTED
        |4| N = NOT SUPPORTED, MUST BE REMOVED
        |2|
        | |
FEAT/PN | |        DESCRIPTION
--------|-|-----------------------------------------
0010    |A| One CSC Billing Unit
0011    |A| Ten USC Billing Units
0050    |A| IBM Express Seller Indicator
0127    |A| Rack Content Specify: 7026/H70 - 8EIA
0128    |A| Rack Content Specify: 7026/H80 - 5EIA
0129    |S| Rack Content Specify: 7026/M80 - 8EIA
0147    |A| Rack Content Specify: 3590/B11 - (2 x B11 = 12EIA)
0149    |A| Rack Content Specify: UPS/MOD - 4EIA
0156    |A| Rack Content Specify: 7133/D40 - 4EIA
0162    |A| Rack Content Specify: 7337/306 - 5EIA
0165    |S| Rack Content Specify: 2104/DL1 - 3EIA
0169    |A| Rack Content Specify: 3490/F11 - 4EIA
0170    |A| Rack Content Specify: 3570/C11 - 6EIA
0171    |A| Rack Content Specify: 3590/E11 - (1X OR 2X = 12EIA)
0172    |A| Rack Content Specify: 3570/C12 - 6EIA
0173    |A| Rack Content Specify: Secondary I/O Drawer, AC Power - 5EIA
0175    |S| Rack Content Specify: 3 EIA
0176    |A| Rack Content Specify: Primary I/O Drawer, - 5EIA
0178    |A| Rack Content Specify: 7026/B80 -- 5 EIA
0179    |A| Rack Content Specify: 2104/DU3 - 3EIA
0180    |A| Rack Content Specify: 2108/G07 - 2EIA
0181    |A| Rack Content Specify: 2109/S08 - 1EIA
0182    |A| Rack Content Specify: 2109/S16 - 2EIA
0183    |A| Rack Content Specify: 9910/A30 - 5EIA
0184    |A| Rack Content Specify:  9910/A31 - 5EIA
0185    |A| Rack Content Specify:  9910/P60 - 6EIA
0186    |A| Rack Content Specify:  9910/P61 - 6EIA
0187    |A| Rack Content Specify:  #6606 -- 3 EIA (9910 UPS
        | |      Battery Module)
0194    |A| Rack Content Specify:  3590/A60 - 9U
0195    |A| Rack Content Specify:  7038/6M2 - 8U
0196    |A| Rack Content Specify:  7311/D10 - (2 x D10 = 4U)
0197    |A| Rack Content Specify:  7028-6C1 -- 5 EIA
0198    |A| Rack Content Specify:  9910/P33 - 2U
0199    |A| Rack Content Specify:  #6607 on 9910-P33 - 2U
0200    |A| Rack Content Specify:  9910/B38 - 4U
0201    |A| Rack Content Specify:  #6621 on 9910-B38 - 2U
0202    |A| Rack Content Specify:  7315/CR2 - 1U
0203    |A| Rack Content Specify:  7026/6H0 - 5U (EIA)
0204    |A| Rack Content Specify:  2104/DS4 - 3EIA
0205    |A| Rack Content Specify:  3592/J1A/E05 - 10EIA
0206    |A| Rack Content Specify:  7028/6C4 - 4U
0207    |A| Rack Content Specify:  7029/6C3 - 4U
0208    |A| Rack Content Specify:  2109/F16 - 1EIA
0210    |A| Rack Content Specify:  7311/D20 - 4U
0213    |A| Rack Content Specify:  3542/2RU - 3EIA (FAST T200)
0214    |A| Rack Content Specify:  3552/1RU - 4EIA (FAST T500)
0215    |A| Rack Content Specify:  3560/1RU - 3EIA (FAST EXP500)
0216    |A| Rack Content Specify:  1 EIA
0217    |A| Rack Content Specify:  3542/2RX - 3EIA (FAST T200 EMEA)
0218    |A| Rack Content Specify:  9910/P18 - 2U
0219    |A| Rack Content Specify:  FC #6606 on 9910-P18 - 2U
0220    |A| Rack Content Specify:  1742/1RU - 4EIA
0221    |A| Rack Content Specify:  1740/1RU - 3EIA
0222    |A| Rack Content Specify:  1742/90U - 4EIA
0223    |A| Rack Content Specify:  3590/H11 - 12EIA
0224    |A| Rack Content Specify: 9910/M15 - 1U
0225    |A| Rack Content Specify: 9910/M30 - 2U
0226    |A| Rack Content Specify: 9910/FC 3401 - 2U
        | |   (9910 UPS Battery Module)
0227    |A| Rack Content Specify: 3592/J70 - 7EIA
0228    |A| Rack Content Specify: 7311/D11 - (2 x D11 = 4U)
0229    |A| Rack Content Specify:  9111/520 - 4U
0230    |A| Rack Content Specify:  9113/550 - 4U
0231    |A| Rack Content Specify: 9117/570/MMA/MMB, 8234-EMA - 4U
0232    |A| Rack Content Specify: 9117/570/MMA/MMB, 8234-EMA - 8U
0234    |A| Rack Content Specify: 1710/10U, 1812/81A, 1818/D1A - 3EIA
        | | (DASD EXP)(AC, 2 Cords)
0233    |A| Rack Content Specify: 7316-TF3 - 1EIA
0235    |A| Rack Content Specify: 1722/60U - 3EIA
0236    |A| Rack Content Specify: 9910/P65 - 3EIA
0241    |A| Rack Content Specify: 9117/570/MMA/MMB - 12U
0242    |A| Rack Content Specify: 9117/570/MMA/MMB - 16U
0243    |A| Rack Content Specify: 9910/P30 - 2EIA
0244    |A| Rack Content Specify: 9910/P30 Battery Module - 2EIA
0245    |A| Rack Content Specify: 9910/P64 - 5EIA
0246    |A| Rack Content Specify: 9910 Feature Number 6641
        | |    (9910-P64,P65 Battery Module) - 3EIA
0247    |A| Rack Content Specify:  7310/CR2 - 1U
0249    |A| Rack Content Specify:  7031-D24-4U
0250    |A| Rack Content Specify:  9124/720 - 4U
0251    |A| Rack Content Specify:  9123/710 - 2EIA
0253    |A| Rack Content Specify:  7310/CR3 - 1U
0254    |A| Rack Content Specify: 1724-100 or 1814-70A/72A --
        | | 3EIA
0255    |A| Rack Content Specify:  9110/510 - 2EIA
0256    |A| Rack Content Specify:  7314-G30 - 4EIA
0257    |A| Rack Content Specify:  9131-52A - 4U
0258    |A| Rack Content Specify:  9133-55A - 4U
0259    |A| Rack Content Specify:  9115/505 - 1U
0260    |A| Rack Content Specify:  9116/561 - 4U
0261    |A| Rack Content Specify:  9116/561 - 8U
0262    |S| Rack Content Specify:  7310/CR4 - 1U
0263    |A| Rack Content Specify FC 5886 - 2EIA
0269    |A| Rack Content Specify:  7048-120 - 1 EIA
0270    |A| Rack Content Specify:  7048-270 - 6 EIA
0274    |A| Rack Content Specify:  7214-1U2 - 1 EIA unit
0275    |A| Rack Content Specify:  1815/80A, 1818/53A - 4EIA (AC, 2 Line
        | | Cords)
0278    |A| Rack Content Specify: 8203-E4A - 4U
0284    |S| Rack Content Specify:  7042-CR4 - 1U
0286    |A| Rack Content Specify for 7042/CR5
0288    |A| Rack Content Specify:  8204-E8A - 4U
0297    |A| Rack Content Specify: 8233-E8B - 4U
0298    |A| Rack Content Specify: 8202-E4B - 4U
0299    |A| Rack Content Specify: 8205-E6B -- 4U
0303    |A| RACK SPECIFY FC 5802
0315    |A| Rack Content Specify:  7036-P14 - 1U
0316    |A| Rack Content Specify:  9110-51A - 2U
0317    |A| Rack Content Specify:  7037-A50 - 5U
0320    |S| Rack Content Specify: 9910-E82/E83- 6 EIA
0321    |S| Rack Content Specify: 9910-E82/E83 -FC 6646/6646
        | | Battery Module 3 EIA
0322    |A| Rack Content Specify:  3580/H3L/H3S - 2U
0323    |A| Rack Content Specify: 5887-2U
0324    |A| Rack Content Specify for 7042/CR6
0326    |A| Rack Content Specify:  3580/L33/L43/S43 - 3U
0327    |A| Rack Content Specify:  3573/L2U - 2U
0328    |A| Rack Content Specify:  3573/L4U - 4U
0331    |A| Rack Content Specify: 7874-024 - 1U
0332    |A| Rack Content Specify: 7874-040 - 4U
0334    |A| Rack Content Specify: 7874-120 - 7U
0335    |A| Rack Content Specify: 7874-240 - 14U
0336    |A| Rack Content Specify 3572/SH3/SH4 - 1EIA
0337    |S| Rack Content Specify: 9910-E50 - 3U
0338    |S| Rack Content Specify: 9910-E50 with Feature 6648
0339    |A| Rack Content Specify, 1818-RS2, 1818-RS3
0340    |A| Rack Content Specify, SAN switch
0343    |A| Rack Content Specify:  3576/L5B - 5U
0345    |A| Rack Content Specify:  3576/E9U - 9U
0346    |A| Rack Content Specify:  3577/L5U -5U
0361    |A| Rack Content Specify 5 EIA for FC 0595
0363    |A| 2EIA Rack Content Specify
0364    |A| Rack Content Specify, Juniper EX4200 Switch
0370    |A| Rack Content Specify: 8231-E2B -- 2U
0379    |A| Rack Content Specify: 7874-036 - 1U
0380    |A| Rack Content Specify: 7874-072 - 5U
0381    |A| Rack Content Specify: 7874-324 - 14U
0384    |A| Rack Content Specify: 9179-MHB, 4U.
0385    |A| Rack Content Specify: 9179-MHB, 8U.
0386    |A| Rack Content Specify: 9179-MHB, 12U.
0387    |A| Rack Content Specify: 9179-MHB, 16U.
0388    |A| Rack Content Specify, Juniper EX4500 Switch
0389    |A| Rack Content Specify, Switch Network Documentation
        | |Drawer
0390    |A| Rack Content Specify, DS3500 Storage Drawer
0392    |A| Rack Content Specify: 8246-Lxx
0458    |A| Rack Content Specify: 5888-1U
0469    |A| Customer Specified Rack Placement
0710    |A| Balanced Warehouse Solution
0711    |S| IBM mCommerce Application Solution Indicator
0712    |A| Manufacturing Routing Code for CSC
1114    |A| Smart Analytics System routing indicator
1140    |A| Custom Service Specify, Rochester Minn, USA
4651    |A| Rack Indicator, Rack #1
4652    |A| Rack Indicator, Rack #2
4653    |A| Rack Indicator, Rack #3
4654    |A| Rack Indicator, Rack #4
4655    |A| Rack Indicator, Rack #5
4656    |A| Rack Indicator, Rack #6
4657    |A| Rack Indicator, Rack #7
4658    |A| Rack Indicator, Rack #8
4659    |A| Rack Indicator, Rack #9
4660    |A| Rack Indicator, Rack #10
4661    |A| Rack Indicator, Rack #11
4662    |A| Rack Indicator, Rack #12
4663    |A| Rack Indicator, Rack #13
4664    |A| Rack Indicator, Rack #14
4665    |A| Rack Indicator, Rack #15
4666    |A| Rack Indicator, Rack #16
4690    |S| Rack Status Beacon
4691    |S| Rack Status Beacon Cable, Junction Box To Drawer Or
        | |      Status Beacon
4692    |S| Rack Status Beacon Cable, Junction Box Daisy Chain
4693    |S| Rack Status Beacon Junction Box
5001    |A| Customer Service Specify
5524    |A| RFID TAGS FOR SERVERS, BLADES, BLADECENTERS, RACKS,
        | |AND HMCS
5889    |A| Intelligent PDU+, base option, 1 EIA Unit,
        | |  Universal, UTG0247 Connector
6069    |A| Front Door For 2.0 Meter Rack (High Perforation)
6080    |A| Ruggedized Rack Feature
6081    |S| Front Trim Kit For 2.0 Meter Rack (Black)
6082    |S| Front Trim Kit For 2.0 Meter Rack (White)
6083    |S| Front Door For 2.0 Meter Rack (Black)
6084    |A| Front Door For 2.0M OEM Rack (Black)
6086    |A| Suite Attach Kit For 2.0 Meter Rack (Black)
6087    |S| Suite Attach Kit For 2.0 Meter Rack (White)
6095    |A| Power Cord for PDU to External I/O Device
6098    |A| Side Panel For 1.8 or 2.0 Meter Rack (Black)
6099    |A| Side Panel For 1.8 Or 2.0 Meter Rack (White)
6171    |S| Power Distribution Unit - Side Mount, Single Phase
6173    |S| Power Distribution Unit - Side Mount, Two Of Three Phase
6238    |A| High-end Appearance Side Covers
6247    |S| Thin Profile Front Trim Kit For 2.0 Meter Rack (Black)
6249    |A| Acoustic Rack Doors, Front and Rear, 2.0 M
6250    |A| High-End Appearance Front Door
6257    |A| Rack Extender
6272    |A| 2.0m Rack Trim Kit
6442    |S| Power Cord, 7176/9176 PDU To Wall, 9800/9824 Equivalent
6443    |S| Power Cord, 7176/9176 PDU To Wall, 9801 Equivalent
6444    |S| Power Cord, 7176/9176 PDU To Wall, 9822 Equivalent
6445    |S| Power Cord, 7177/9177 PDU To Wall, 9823 Equivalent
6447    |S| Power Cord, 7176/9176 PDU To Wall, 9826 Equivalent
6448    |S| Power Cord, 7176/9176 PDU To Wall, 9835 Equivalent
6449    |S| Power Cord, 7176/9176 PDU To Wall, 9986 Equivalent
6450    |S| Power Cord, 7176/9176 PDU To Wall, 9987 Equivalent
6489    |A| Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, IEC 309
        | |      3P+N+G 32A Plug
6491    |A| Power Cord, 7188/9188 PDU To Wall, 4.3M, 48A, IEC 309
        | |      P+N+G 63A Plug
6492    |A| Power Cord, 7188/9188 PDU To Wall, 4.3M, 48A, IEC 309
        | |      2P+G 60A Plug
6546    |S| White Rack Option, Factory Only
6580    |A| Rack Security Kit
6586    |A| Modem Tray For 19-Inch Rack
6653    |A| Power Cord, 7188/9188 PDU To Wall, 4.3M, 16A, IEC 309
        | |      3P+N+G 16A Plug
6654    |A| Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, NEMA L6-30
        | |      Plug
6655    |A| Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, RS 3750DP
        | |      (Watertight) Plug
6656    |A| Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, IEC 309
        | |      P+N+G 32A Plug
6657    |A| Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, PDL Plug
6658    |A| Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, Korean Plug
6667    |A| 4.3m (14-Ft) 3PH/32A Pwr Cd-Australia
6858    |A| Rear Door Heat Exchanger for 7014-T42
6860    |A| Mounting hardware kit
7109    |A| Intelligent PDU+, 1 EIA Unit, Universal, UTG0247
        | |  Connector
7118    |A| Environmental Monitoring Probe
7176    |S| Power Distribution Unit - Side Mount, Single Phase, L6-30
        | |      Connector
7177    |S| Power Distribution Unit - Side Mount, Single Phase,
        | |      IEC-309 Connector
7178    |S| Power Distribution Unit - Side Mount, Three Phase,
        | |      IEC-309 Connector
7188    |A| Power Distribution Unit - Side Mount, Universal, UTG0247
        | |      Connector
9002    |A| Field Integration Indicator, Ship Empty Rack
9169    |A| Order Routing Indicator - System Plant
9171    |S| Power Distribution Unit Specify - Base/Side Mount, Single
        | |      Phase
9173    |S| Power Distribution Unit Specify - Base/Side Mount, Two Of
        | |      Three Phase
9176    |S| Power Distribution Unit Specify - Base/Side Mount, Single
        | |      Phase, L6-30 Connector
9177    |S| Power Distribution Unit Specify - Base/Side Mount, Single
        | |      Phase, IEC-309 Connector
9178    |S| Power Distribution Unit Specify - Base/Side Mount, Three
        | |      Phase, IEC-309 Connector
9188    |A| Power Distribution Unit Specify - Base/Side Mount,
        | |      Universal, UTG0247 Connector
9300    |A| Language Group Specify - US English
9459    |A| PDU/PWR and Power Cord Redundancy Assurance
9703    |A| Language Group Specify - French
9704    |A| Language Group Specify - German
9705    |A| Language Group Specify - Polish
9707    |A| Language Group Specify - Portuguese
9708    |A| Language Group Specify - Spanish
9711    |A| Language Group Specify - Italian
9712    |A| Language Group Specify - Canadian French
9714    |A| Language Group Specify - Japanese
9716    |A| Language Group Specify - Korean
9719    |A| Language Group Specify - Hungarian
9720    |A| Language Group Specify - Slovakian
9721    |A| Language Group Specify - Russian
9722    |A| Language Group Specify - Simplified Chinese (PRC)
9800    |S| Power Cord Specify - United States/Canada
9801    |S| Power Cord Specify - Raised Floor (US)
9822    |S| Power Cord Specify - Australia
9823    |S| Power Cord Specify - EMEA (PDU)
9824    |S| Power Cord Specify - Japan and 60HZ AP
9826    |S| Power Cord Specify - New Zealand
9835    |S| Power Cord Specify - Korea (PDU)
9986    |S| Power Cord Specify - Chicago (1.8M)(6 FT.)
9987    |S| Power Cord Specify - Chicago (Raised Floor)
ECSC    |A| Custom Service Specify, Shenzhen, China
ECSM    |A| Custom Service Specify, Mexico
ECSP    |A| Custom Service Specify, Poughkeepsie, USA
ECSS    |A| Integrated Solution Packing
EDAN    |A| Analytics Data Node Add-on
EGSA    |A| IDEA Solution Specify
EGSB    |A| SOLUTION SPECIFY
EGSC    |A| GL2 SOLUTION SPEC 2TB DCS370E
EGSD    |A| GL4 SOLUTION SPEC 2TB DCS370E
EGSE    |A| GL6 SOLUTION SPEC 2TB DCS370E
EGSF    |A| GL2 SOLUTION SPEC 4TB DCS370E
EGSG    |A| GL4 SOLUTION SPEC 4TB DCS370E
EGSH    |A| GL6 SOLUTION SPEC 4TB DCS370E
EGSJ    |A| GS1 SOLUTION SPEC 400GB #EL1S
EGSK    |A| GS1 SOLUTION SPEC 800GB #EL1S
EGSL    |A| GS2 SOLUTION SPEC 400GB #EL1S
EGSM    |A| GS2 SOLUTION SPEC 800GB #EL1S
EGSN    |A| GS2 SOLUTION SPEC 1.2TB #EL1S
EGSP    |A| GS4 SOLUTION SPEC 400GB #EL1S
EGSQ    |A| GS4 SOLUTION SPEC 800GB #EL1S
EGSR    |A| GS4 SOLUTION SPEC 1.2TB #EL1S
EGSS    |A| GS6 SOLUTION SPEC 1.2TB #EL1S
ERLR    |A| Left/Right PDU Redundancy
ER00    |A| Custom Soln Center Services per PRPQ 8A2064
ER02    |A| Rack Content Specify: 8408-E8D
ER03    |A| Rack Content Specify: 2076-224 - 2U
ER04    |A| Rack Content Specify: 2076-124 - 2U
ER07    |A| Rack Content Specify: 1611-16E 1EIA (BINGO)
ER08    |A| Rack Content Specify: 1455-24E
ER09    |A| Rack Content Specify: 1455-48E
ER0A    |A| Rack Content Specify: 1455-64C
ER0B    |A| Rack Content Specify: 1455-48T
ER0C    |A| Rack Content Specify: 1455-64F
ER0D    |A| Rack Content Specify: 9109-RMD
ER0E    |A| Rack Content Specify: 7316-TF4 -- 1 EIA
ER0H    |A| Rack Content Specify: 8248-L4T
ER0J    |A| Rack Content Specify: 8412-EAD
ER0M    |A| Rack Content Specify for #EMX0 I/O Expansion Drawer
ER0T    |A| Rack Content Specify 8286-41A/42A - 4EIA
ER0U    |A| Rack Content Specify: 8284-22A - 2EIA
ER0V    |A| Rack Content Specify: 8247-21L/22L - 2EIA
ER0Y    |A| Rack Content Specify: 8412-EAD
ER0Z    |A| Rack Content Specify: 8247-42L - 4EIA
ER10    |A| Rack Content Specify first enclosure: 9119-MHE,
        | |9119-MME - 7 EIA
ER11    |A| Rack Content Specify second enclosure: 9119-MHE,
        | |9119-MME - 12 EIA
ER12    |A| Rack Content Specify third enclosure: 9119-MHE,
        | |9119-MME - 17 EIA
ER13    |A| Rack Content Specify fourth enclosure: 9119-MHE,
        | |9119-MME - 22 EIA
ER14    |A| Rack Content Specify 1U Horizontal PDU: 9119-MHE,
        | |9119-MME - 1 EIA
ER15    |A| Rack Content Specify reserve 5U rack space: 9119-MHE,
        | |9119-MME
ER18    |A| Rack Content Specify: 8247-21L - 2EIA
ER19    |A| RACK SPECIFY FC EMX0
ER1B    |A| Rack Content Specify: Reserve 1U Rack Space at Bottom of Rack
ER1F    |A| FlashSystem 9840/9843 - 2 E1A
ER1T    |A| Rack Content Specify: Reserve 1U Rack Space at Top of Rack
ER2B    |A| Rack Content Specify: Reserve 2U Rack Space at Bottom
        | |of Rack
ER2T    |A| Rack Content Specify: Reserve 2U Rack Space at Top of
        | |Rack
ERG0    |A| Rack Rear Extension
ERG7    |A| Front Door for Power 770 & 780 2.0 Meter Rack (High
        | |Perforation)
ESC0    |A| S&H - No Charge
ESC1    |A| Rack S&H-a
 

Back to topBack to top
 
Models

Model summary matrix

Model    Capacity
-----    ---------------------------------------
 T42     42 EIA units of vertical mounting space
 

Customer setup (CSU)

These products are designated Customer Setup.

Devices supported

None

Model conversions

None
Back to topBack to top
 
Technical description
TOC Link Physical specifications TOC Link Operating environment TOC Link Limitations
TOC Link Hardware requirements TOC Link Software requirements


This 2.0 meter rack has 42 EIA units of vertical mounting space for 19-inch mounting-width drawers. The standard rack comes with an AC power distribution unit rear-mounted in an area that is separate from the drawer mounting area.

Physical specifications

Physical Specifications Rack Model T42:

Operating environment

Power Requirements:

Rack Model T42

The rack power distribution system provides 200 to 240 V AC (50Hz/60Hz) to the system components (drawers). Each Power Distribution Unit (PDU) is capable of providing up to 4.8 KVA.

EMC Conformance Classification:

This equipment is subject to FCC rules; it will comply with the appropriate FCC rules before final delivery to the buyer or center of distribution.

EMC Conformance:

Taiwan BCIQ CNS13438 (Taiwan EMC Standard)

Homologation: Telecom Environmental Testing (Safety and EMC)

Homologation approval for specific countries has been initiated with the IBM Homologation and Type Approval (HT&A) organization in LaGaude, France.

The 7014 and applicable features meet the environmental testing requirements of the country TELECOM and have been designed and tested in compliance with the Full Quality Assurance Approval (FQAA) process as delivered by the British Approval Board for Telecom (BABT), the UK Telecom Regulatory authority.

General Requirements

This product complies with the IBM Corporate Bulletin C-B 0-2594-000 Statement of Conformity of IBM Product to External Standard (Suppliers Declaration).

Product Safety/Country Testing/Certification

The following information must be entered per Energy Saving Law - Japan, Program Requirements Number N-B 1-9174-001.

Power Requirements

Limitations

Models T42:

Hardware requirements

Supported PDU Combinations for 7014 Models T00 and T42

Each 7014-T00 or 7014-T42 rack is shipped with one of the available base PDU features. The choice of which initial PDU is ordered for the rack will determine which additional PDU features may be ordered for the rack, either in the original rack order or in a later MES order. The following chart shows the allowable PDU combinations within a single T00 or T42 rack.

             |------------------------------------------------|
             |       Allowable Optional/Additional PDUs       |
             |------|------|------|------|------|------|------|
             | 6171 | 6173 | 6174 | 7176 | 7177 | 7178 | 7188 |
=============|======|======|======|======|======|======|======|
|     | 9171 |  X   |      |      |  M(1)|  M(2)|      |      |
|     | -----|------|------|------|------|------|------|------|
|  B  | 9173 |      |  X   |      |      |      |  M+  |      |
|  A  | -----|------|------|------|------|------|------|------|
|  S  | 9174 |      |      |  X   |      |      |  M   |      |
|  E  | -----|------|------|------|------|------|------|------|
|     | 9176 |      |      |      |  X   |      |      |      |
|  P  | -----|------|------|------|------|------|------|------|
|  D  | 9177 |      |      |      |      |  X   |      |      |
|  U  | -----|------|------|------|------|------|------|------|
|     | 9178 |      |      |      |      |      |  X   |      |
|     | -----|------|------|------|------|------|------|------|
|     | 9188 |      |      |      |      |      |      |  X   |
|-----| -----|------|------|------|------|------|------|------|
 
9188 as the last row for BASE PDU 7188 Allowable Optional/Additional PDUs

Software requirements

Not applicable
Back to topBack to top
 
Publications

Model T00 and T42 Rack Installation and Service Guide (SA38-0577) is shipped with the products.
Back to topBack to top
 
Features
TOC Link Features - No charge TOC Link Features - Chargeable TOC Link Feature descriptions
TOC Link Feature exchanges


Features - No charge

COLOR: Black. A specify code is not required.

VOLTAGE: A specify code for voltage/power is required and will be provided by the configurator based on the country code of the order. Specify codes must be used when an alternative to the ELINK configurator default is required.

LANGUAGE: A specify code is not required. Language will be determined by the plant based on the country code of the order. Specify codes must be used when an alternative to the plant country default is required.

Features - Chargeable

Special Features - Initial Orders

Special Features - Plant and/or Field Installable

Feature descriptions

The following is a list of all feature codes in numeric order.

Attributes, as defined in the following feature descriptions, state the interaction of requirements among features.

Minimums and maximums are the absolute limits for a single feature without regard to interaction with other features. The maximum valid quantity for MES orders may be different than for initial orders. The maximums listed below refer to the largest quantity of these two possibilities.

The order type defines if a feature is orderable only on initial orders, only on MES orders, on both initial and MES orders, or if a feature is supported on a model due to a model conversion. Supported features cannot be ordered on the converted model, only left on or removed from the converted model.

(#0010) - One CSC Billing Unit

One CSC Billing Unit

(#0011) - Ten USC Billing Units

Ten CSC Billing Units

(#0050) IBM Express Seller Indicator

This feature is a no-charge feature used for administrative purposes by IBM and IBM Business Partners.

(#0127) Rack Content Specify: 7026/H70 - 8EIA

(#0128) Rack Content Specify: 7026/H80 - 5EIA

Indicator of rack space utilization.

(#0129) Rack Content Specify: 7026/M80 - 8EIA

(No Longer Available as of June 23, 2006)

Indicator of rack space utilization.

(#0147) Rack Content Specify: 3590/B11 - (2 x B11 = 12EIA)

Indicator of rack space utilization for 3590/B11, Disk Drawer.

(#0149) Rack Content Specify: UPS/MOD - 4EIA

Indicator of rack space utilization.

(#0156) Rack Content Specify: 7133/D40 - 4EIA

Indicator of rack space utilization.

(#0162) Rack Content Specify: 7337/306 - 5EIA

Indicator of rack space utilization.

(#0165) Rack Content Specify: 2104/DL1 - 3EIA

(No Longer Available as of June 28, 2002)

Indicator of rack space utilization.

(#0169) Rack Content Specify: 3490/F11 - 4EIA

Indicator of rack space utilization.

(#0170) Rack Content Specify: 3570/C11 - 6EIA

Indicator of rack space utilization.

(#0171) Rack Content Specify: 3590/E11 - (1X OR 2X = 12EIA)

Indicator of rack space utilization.

(#0172) Rack Content Specify: 3570/C12 - 6EIA

Indicator of rack space utilization.

(#0173) Rack Content Specify: Secondary I/O Drawer, AC Power - 5EIA

Indicator of rack space utilization.

(#0175) Rack Content Specify: 3 EIA

(No Longer Available as of September 13, 2002)

(#0176) Rack Content Specify: Primary I/O Drawer, - 5EIA

Indicator of rack space utilization.

(#0178) Rack Content Specify: 7026/B80 -- 5 EIA

(#0179) Rack Content Specify: 2104/DU3 - 3EIA

(#0180) Rack Content Specify: 2108/G07 - 2EIA

(#0181) Rack Content Specify: 2109/S08 - 1EIA

(#0182) Rack Content Specify: 2109/S16 - 2EIA

(#0183) Rack Content Specify: 9910/A30 - 5EIA

(#0184) Rack Content Specify: 9910/A31 - 5EIA

(#0185) Rack Content Specify: 9910/P60 - 6EIA

(#0186) Rack Content Specify: 9910/P61 - 6EIA

(#0187) Rack Content Specify: FC 6606 -- 3 EIA (9910 UPS Battery Module)

(#0188) Rack Content Specify: 7026/6H1 - 5EIA

Indicator of rack space utilization.

(#0189) Rack Content Specify: 7026/6M1 - 8EIA (CEC Drawer)

Indicator of rack space utilization.

(#0194) Rack Content Specify: 3590/A60 - 9U

Indicator of rack space utilization.

(#0195) Rack Content Specify: 7038/6M2 - 8U

Indicator of rack space utilization.

(#0196) Rack Content Specify: 7311/D10 - (2 x D10 = 4U)

Indicator of rack space utilization.

(#0197) Rack Content Specify: 7028-6C1 -- 5 EIA

Indicator of rack space utilization.

(#0198) Rack Content Specify: 9910/P33 - 2U

Indicator of rack space utilization.

(#0199) Rack Content Specify: FC #6607 on 9910-P33 - 2U

Indicator of rack space utilization.

Note: Maximum of four per feature #0198.

(#0200) Rack Content Specify: 9910/B38 - 4U

Indicator of rack space utilization.

(#0201) Rack Content Specify: FC #6621 on 9910-B38 - 2U

Indicator of rack space utilization.

(#0202) Rack Content Specify: 7315/CR2 - 1U

Indicator of rack space utilization.

(#0203) Rack Content Specify: 7026/6H0 - 5U (EIA)

Indicator of rack space utilization.

(#0204) Rack Content Specify: 2104/DS4 - 3EIA

(#0205) Rack Content Specify: 3592/J1A/E05 - 10EIA

Note: Each model 3592-J1A or E05 occupies half of the rack width for the full 10 EIA height. Two of these models can share the same 10 EIA rack space.

(#0206) Rack Content Specify: 7028/6C4 - 4U

Indicator of rack space utilization.

(#0207) Rack Content Specify: 7029/6C3 - 4U

Indicator of rack space utilization.

(#0208) Rack Content Specify: 2109/F16 - 1EIA

(#0210) Rack Content Specify: 7311/D20 - 4U

Indicator of rack space utilization.

(#0213) Rack Content Specify: 3542/2RU - 3EIA (FAST T200)

(#0214) Rack Content Specify: 3552/1RU - 4EIA (FAST T500)

(#0215) Rack Content Specify: 3560/1RU - 3EIA (FAST EXP500)

(#0216) Rack Content Specify : 7316/TF2 - 1 EIA:

(#0217) Rack Content Specify: 3542/2RX - 3EIA (FAST T200 EMEA)

(#0218) Rack Content Specify: 9910/P18 - 2U

Indicator of rack space utilization.

(#0219) Rack Content Specify: FC #6606 on 9910-P18 - 2U

Indicator of rack space utilization.

(#0220) Rack Content Specify: 1742/1RU - 4EIA

(#0221) Rack Content Specify: 1740/1RU - 3EIA

(#0222) Rack Content Specify: 1742/90U - 4EIA

(#0223) Rack Content Specify: 3590/H11 - 12EIA

(#0224) Rack Content Specify: 9910/M15 - 1U

(#0225) Rack Content Specify: 9910/M30 - 2U

(#0226) Rack Content Specify: FC #3401 on 9910/M30 - 2U (9910 UPS Battery Module)

(#0227) Rack Content Specify: 3592/J70 - 7EIA

(#0228) Rack Content Specify: 7311/D11 - (2 x D11 = 4U)

Indicator of rack space utilization.

(#0229) Rack Content Specify: 9111/520 - 4U

Indicator of rack space utilization.

(#0230) Rack Content Specify: 9113/550 - 4U

Indicator of rack space utilization.

(#0231) Rack Content Specify: 9117/570/MMA/MMB, 8234-EMA - 4U

Indicator of rack space utilization.

(#0232) Rack Content Specify: 9117/570/MMA/MMB, 8234-EMA - 8U

Indicator of rack space utilization.

(#0233) Rack Content Specify: 7316-TF3 -- 1 EIA

Indicator of rack space utilization.

(#0234) Rack Content Specify: 1710/10U, 1812/81A, 1818/D1A - 3EIA

(DASD EXP)(AC, 2 Cords)

(#0235) Rack Content Specify: 1722/60U - 3EIA

(#0236) Rack Content Specify: 9910/P65 - 3EIA

(#0241) Rack Content Specify: 9117/570/MMA/MMB - 12U

Indicator of rack space utilization.

(#0242) Rack Content Specify: 9117/570/MMA/MMB - 16U

Indicator of rack space utilization.

(#0243) Rack Content Specify: 9910/P30 - 2EIA

(#0244) Rack Content Specify: 9910/P30 Battery Module - 2EIA

(#0245) Rack Content Specify: 9910/P64 - 5EIA

(#0246) Rack Content Specify: 9910 Feature Number 6641 (9910-P64, P65 Battery Module) - 3EIA

(#0247) Rack Content Specify: 7310/CR2 - 1U

Indicator of rack space utilization.

(#0249) Rack Content Specify: 7031-D24-4U

Indicator of rack space utilization.

(#0250) Rack Content Specify: 9124/720 - 4U

Indicator of rack space utilization.

(#0251) Rack Content Specify: 9123/710 - 2EIA

(#0252) Rack Content Specify: 7315/CR3 1U

Indicator of rack space utilization.

(#0253) Rack Content Specify: 7310/CR3 1U

Indicator of rack space utilization.

(#0254) Rack Content Specify: 1724-100 or 1814-70A/72A -- 3EIA

Indicator of rack space utilization.

(#0255) Rack Content Specify: 9110/510 - 2EIA

(#0256) Rack Content Specify: 7314-G30 -4 EIA

Indicator of rack space utilization.

(#0257) Rack Content Specify: 9131-52A - 4U

Indicator of rack space utilization.

(#0258) Rack Content Specify: 9133-55A - 4U

Indicator of rack space utilization.

(#0259) Rack Content Specify: 9115/505 - 1U

Indicator of rack space utilization.

(#0260) Rack Content Specify: 9116/561 - 4U

Indicator of rack space utilization.

(#0261) Rack Content Specify: 9116/561 - 8U

Indicator of rack space utilization.

(#0262) Rack Content Specify: 7310/CR4 1U

(No Longer Available as of November 27, 2009)

Indicator of rack space utilization.

(#0263) Rack Content Specify FC 5886 - 2EIA

Indicator of rack space utilization.

(#0269) Rack Content Specify 7048-120 - 1 EIA

(No Longer Available as of June 23, 2006)

Indicator of rack space utilization for 7048-120

(#0270) Rack Content Specify 7048-270 - 6 EIA

(No Longer Available as of June 23, 2006)

Indicator of rack space utilization for 7048-270.

(#0274) Rack Content Specify: 7214-1U2 - 1 EIA unit

Indicator of rack space utilization.

(#0275) Rack Content Specify: 1815/80A, 1818/53A - 4EIA (AC, 2 Line

Cords)

Indicator of rack space utilization.

(#0278) Rack Content Specify: 8203-E4A - 4U

Indicator of rack space utilization

(#0284) Rack Content Specify 7042-CR4 1U

(No Longer Available as of December 31, 2009)

Indicator of rack space utilization.

(#0286) - Rack Content Specify for 7042/CR5

(#0288) Rack Content Specify: 8204-E8A - 4U

Indicator of rack space utilization.

(#0297) - Rack Content Specify: 8233-E8B - 4U

(#0298) - Rack Content Specify: 8202-E4B - 4U

Indicator of rack space utilization.

(#0299) - Rack Content Specify: 8205-E6B -- 4U

Indicator of rack space utilization.

(#0303) - RACK SPECIFY FC 5802

Allocate 4EA space in the rack for #5802.

(#0315) Rack Content Specify: 7036-P16 - 1U

Indicator of rack space utilization

(#0316) Rack Content Specify: 9110-51A - 2U

Indicator of rack space utilization.

(#0317) Rack Content Specify: 7037-A50 - 5U

Indicator of rack space utilization.

(#0320) Rack Content Specify: 9910-E82/E83- 6 EIA

(No Longer Available as of September 10, 2013)

Indicator of rack space utilization.

(#0321) Rack Content Specify: 9910-E82/E83 FC 6646/6646 Battery Module 3 EIA

(No Longer Available as of September 10, 2013)

Indicator of rack space utilization.

(#0322) Rack Content Specify: 3580/H3L/H3S - 2U

Indicator of rack space utilization.

(#0323) - Rack Content Specify: 5887-2U

Indicator of rack space utilization

(#0324) - Rack Content Specify for 7042/CR6

(#0326) Rack Content Specify: 3580/L33/L43/S43 - 3U

Indicator of rack space utilization.

(#0327) Rack Content Specify: 3573/L2U - 2U

Indicator of rack space utilization.

(#0328) Rack Content Specify: 3573/L4U - 4U

Indicator of rack space utilization.

(#0331) Rack Content Specify: 7874-024 - 1U

Indicator of rack space utilization.

(#0332) Rack Content Specify: 7874-040 - 4U

Indicator of rack space utilization.

(#0334) Rack Content Specify: 7874-120 - 7U

Indicator of rack space utilization.

(#0335) Rack Content Specify: 7874-240 - 14U

Indicator of rack space utilization.

(#0336) Rack Content Specify 3572/SH3/SH4 - 1EIA

Rack Content Specify 3572/SH3/SH4 - 1EIA

(#0337) - Rack Content Specify: 9910-E50 - 3U

(No Longer Available as of September 10, 2013)

Indicator of rack space utilization

(#0338) Rack Content Specify: 9910-E50 with Feature 6648

(No Longer Available as of September 10, 2013)

Indicator of rack space utilization

(#0339) Rack Content Specify, 1818-RS2, 1818-RS3

(#0340) Rack Content Specify, SAN switch

(#0343) Rack Content Specify: 3576/L5B - 5U

Indicator of rack space utilization.

(#0345) Rack Content Specify: 3576/E9U - 9U

Indicator of rack space utilization.

(#0346) Rack Content Specify: 3577/L5U -5U

Indicator of rack space utilization.

(#0361) Rack Content Specify 5 EIA for FC 0595

Rack Indicator of rack space utilization.

(#0363) - 2EIA Rack Content Specify

Allocate one 2EIA (2U) space in the rack for one IBM 2076 Storwize V7000 Control Enclosure. (2076-112/124/212/224/312 /324)

(#0364) Rack Content Specify, Juniper EX4200 Switch

(#0370) - Rack Content Specify: 8231-E2B -- 2U

Indicator of rack space utilization.

(#0379) - Rack Content Specify: 7874-036 - 1U

Indicator of rack space utilization.

(#0380) - Rack Content Specify: 7874-072 - 5U

Indicator of rack space utilization.

(#0381) - Rack Content Specify: 7874-324 - 14U

Indicator of rack space utilization.

(#0384) - Rack Content Specify: 9179-MHB, 4U.

Rack Content Specify Code for a single enclosure (4U) 9179-MHB to indicate rack space utilization.

(#0385) - Rack Content Specify: 9179-MHB, 8U.

Rack Content Specify Code for a two enclosure (8U) 9179-MHB to indicate rack space utilization.

(#0386) - Rack Content Specify: 9179-MHB, 12U.

Rack Content Specify Code for a three enclosure (12U) 9179-MHB to indicate rack space utilization.

(#0387) - Rack Content Specify: 9179-MHB, 16U.

Rack Content Specify Code for a four enclosure (16U) 9179-MHB to indicate rack space utilization.

(#0388) - Rack Content Specify, Juniper EX4500 Switch

(#0389) - Rack Content Specify, Switch Network Documentation Drawer

(#0390) - Rack Content Specify, DS3500 Storage Drawer

(#0392) - Rack Content Specify: 8246-Lxx

(#0458) - Rack Content Specify: 5888-1U

Indicator of rack space utilization

(#0469) Customer Specified Rack Placement

Provides the customer the ability to specify the physical location of the system drawers and attached expansion drawers in the rack. The customer's input is collected and verified via the marketing configurator. The Clients request will be reviewed for safe handling by checking weight distribution within the rack. Final approval for the requested drawer placement location will be provided by the Manufacturing Plant. This information is then used by IBM Manufacturing to assemble the system components (drawers) in the rack accordinating to the Clients request.

The CFReport from the marketing configurator must be submitted to:

www.ibm.com/servers/eserver/power/csp

(US Business Partners and Distributors can bypass this step.)

If #0469 is not on the initial rack order, component placement within the rack will be determined by IBM.

(#0703) Solution Indicator

(No Longer Available as of December 31, 2002)

This feature is required when ordering certain Infrastructure offerings. It is for administrative use only and provides no parts.

(#0704) HA Solution Indicator

(No Longer Available as of December 31, 2002)

This feature is required when ordering certain High Availability Infrastructure offerings. It is for administrative use only and provides no parts.

(#0710) Balanced Warehouse Solution:

This feature specifies that the DS4000 EXP810 ordered will be a component of the Balanced Warehouse Solution. This feature will automatically be selected by the configurator when a Balanced Warehouse solution is configured. The solution will be integrated at the Customer Solution Center.

(#0711) - IBM mCommerce Application Solution Indicator

(No Longer Available as of December 31, 2012)

This feature specifies a 8233-E8B server, 7042-CR6 (HMC), 7014-T42 (rack), and 7318-TF3 (console) configuration for the IBM mCommerce Application Solution. The solution will be integrated at the Customer Solution Center.

(#0712) - MANUFACTURING ROUTING CODE FOR CSC

A manufacturing routing code used to route orders to the Custom Solution Center for assembly

(#1114) Smart Analytics System routing indicator

(#1140) - Custom Service Specify, Rochester Minn, USA

Having #1140 on the order, will cause the order to be routed to Rochester and the machine to be internally routed to the CSC build area in building 114 (Rochester).

(#4651) Rack Indicator, Rack #1

When added to an initial rack order, this indicator is used to specify the first rack for a multi-rack order, or the only rack for a single rack order. When added to an initial rack-mountable device order this indicator is used to specify that the rack-mountable device (such as a system or I/O drawer) is to be mounted in rack #1 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4652) Rack Indicator, Rack #2

When added to an initial rack order, this indicator is used to specify the second rack for a multi-rack order. When added to an initial rack- mountable device order, this indicator is used to specify that the rack- mountable device (such as a system or I/O drawer) is to be mounted in rack #2 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4653) Rack Indicator, Rack #3

When added to an initial rack order, this indicator is used to specify the third rack for a multi-rack order. When added to an initial rack- mountable device order, this indicator is used to specify that the rack- mountable device (such as a system or I/O drawer) is to be mounted in rack #3 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4654) Rack Indicator, Rack #4

When added to an initial rack order, this indicator is used to specify the fourth rack for a multi-rack order. When added to an initial rack- mountable device order, this indicator is used to specify that the rack- mountable device (such as a system or I/O drawer) is to be mounted in rack #4 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4655) Rack Indicator, Rack #5

When added to an initial rack order, this indicator is used to specify the fifth rack for a multi-rack order. When added to an initial rack- mountable device order, this indicator is used to specify that the rack- mountable device (such as a system or I/O drawer) is to be mounted in rack #5 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4656) Rack Indicator, Rack #6

When added to an initial rack order, this indicator is used to specify the sixth rack for a multi-rack order. When added to an initial rack- mountable device order, this indicator is used to specify that the rack- mountable device (such as a system or I/O drawer) is to be mounted in rack #6 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4657) Rack Indicator, Rack #7

When added to an initial rack order, this indicator is used to specify the seventh rack for a multi-rack order. When added to an initial rack- mountable device order, this indicator is used to specify that the rack- mountable device (such as a system or I/O drawer) is to be mounted in rack #7 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4658) Rack Indicator, Rack #8

When added to an initial rack order, this indicator is used to specify the eighth rack for a multi-rack order. When added to an initial rack- mountable device order, this indicator is used to specify that the rack- mountable device (such as a system or I/O drawer) is to be mounted in rack #8 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4659) Rack Indicator, Rack #9

When added to an initial rack order, this indicator is used to specify the ninth rack for a multi-rack order. When added to an initial rack- mountable device order, this indicator is used to specify that the rack- mountable device (such as a system or I/O drawer) is to be mounted in rack #9 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4660) Rack Indicator, Rack #10

When added to an initial rack order, this indicator is used to specify the tenth rack for a multi-rack order. When added to an initial rack- mountable device order, this indicator is used to specify that the rack- mountable device (such as a system or I/O drawer) is to be mounted in rack #10 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4661) Rack Indicator, Rack #11

When added to an initial rack order, this indicator is used to specify the eleventh rack for a multi-rack order. When added to an initial rack- mountable device order, this indicator is used to specify that the rack- mountable device (such as a system or I/O drawer) is to be mounted in rack #11 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4662) Rack Indicator, Rack #12

When added to an initial rack order, this indicator is used to specify the twelfth rack for a multi-rack order. When added to an initial rack- mountable device order, this indicator is used to specify that the rack- mountable device (such as a system or I/O drawer) is to be mounted in rack #12 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4663) Rack Indicator, Rack #13

When added to an initial rack order, this indicator is used to specify the thirteenth rack for a multi-rack order. When added to an initial rack-mountable device order, this indicator is used to specify that the rack-mountable device (such as a system or I/O drawer) is to be mounted in rack #13 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4664) Rack Indicator, Rack #14

When added to an initial rack order, this indicator is used to specify the fourteenth rack for a multi-rack order. When added to an initial rack-mountable device order, this indicator is used to specify that the rack-mountable device (such as a system or I/O drawer) is to be mounted in rack #14 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4665) Rack Indicator, Rack #15

When added to an initial rack order, this indicator is used to specify the fifteenth rack for a multi-rack order. When added to an initial rack-mountable device order, this indicator is used to specify that the rack-mountable device (such as a system or I/O drawer) is to be mounted in rack #15 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4666) Rack Indicator, Rack #16

When added to an initial rack order, this indicator is used to specify the sixteenth rack for a multi-rack order. When added to an initial rack-mountable device order, this indicator is used to specify that the rack-mountable device (such as a system or I/O drawer) is to be mounted in rack #16 of a multi-rack order.

Note: For 19" rack-mountable device orders: One feature code from the group 4650 to 4666 must be listed on the order. More than one feature code from this group is not allowed.

For 19" rack orders: If IBM Mfg. is to assemble a rack mountable device into the rack, one feature code selection from the group 4651 to 4666 must be listed on the order. More than one feature code selection from this group is not allowed. The quantity of this selected feature code on the 19" rack order must equal the number of rack mountable devices to be installed in the rack by IBM Mfg.

(#4690) Rack Status Beacon

(No Longer Available as of November 18, 2005)

The Rack Status Beacon is designed to be placed on the top of a rack and cabled to multiple components inside the rack. Servers in the rack can be programmed to illuminate the beacon in response to any detected problems or changes in status. The Rack Status Beacon has redundant AC power inputs and draws its power from the rack Power Distribution Unit (PDU) outlets. At least one #6095 power cord must be ordered to connect the Rack Status Beacon to the PDU.

(#4691) Rack Status Beacon Cable, Junction Box To Drawer Or Status Beacon

(No Longer Available as of November 18, 2005)

This cable can be used to connect the Rack Status Beacon Junction Box to a supported rack drawer or to the Rack Status Beacon.

(#4692) Rack Status Beacon Cable, Junction Box Daisy Chain

(No Longer Available as of March 31, 2006)

This cable is used to connect two Rack Status Beacon Junction Boxes (#4693) together. Multiple Junction Boxes may be linked in series, as required.

(#4693) Rack Status Beacon Junction Box

(No Longer Available as of November 18, 2005)

This feature provides six input connectors and one output connector for racks configured with the Rack Status Beacon (#4690). Multiple Junction Boxes can be linked together in series with Daisy Chain Cable #4692.

(#5001) Customer Service Specify

This feature code specifies that the system will receive special request services from the Customer Solution Center (CSC).

(#5524) RFID TAGS FOR SERVERS, BLADES, BLADECENTERS, RACKS, AND HMCS

The specify feature attaches one Radio Frequency Identification Device (RFID) tag to a Server CEC, rack, HMC, Blade or Bladecenter enclosure. This can be used with MTM (machine type model) rack such as a 7014-T42, not a feature code rack such as a #0553. It applies to newly shipped MTM servers, racks, HMCs, Blades or Bladecenter enclosures, not MES orders with one exception. POWER5 CECs being upgraded to a POWER6 CEC can order this feature. The RFID tag meets the Financial Services Technology Consortium (FSTC) specifications for IT Data Center Asset Tracking.

(#5889) Intelligent PDU+, base option, 1 EIA Unit, Universal, UTG0247 Connector

This feature is for an intelligent AC power distribution unit (PDU+) that will allow the user to monitor the amount of power being used by the devices that are plugged in to this PDU+. This AC power distribution unit provides twelve C13 power outlets. It receives power through a UTG0247 connector. It can be used for many different countries and applications by varying the PDU to Wall Power Cord, which must be ordered separately. Each PDU requires one PDU to Wall Power Cord. Supported power cords include the following features: #6489, #6491, #6492, #6653, #6654, #6655, #6656, #6657, and #6658. This feature should be used only to replace the initial standard PDU, feature 9188, in the base rack definition. This PDU+ is added as a second or greater PDU to a rack by ordering feature 7109.

(#6069) Front Door For 2.0 Meter Rack (High Perforation)

This feature provides an attractive black full height rack door. The door is steel, with a perforated flat front surface. The perforation pattern extends from the bottom to the top of the door to enhance ventilation and provide some visibility into the rack.

(#6080) Ruggedized Rack Feature

For enhanced rigidity and stability of the rack, the optional Ruggedized Rack Feature provides additional hardware that reinforces the rack and anchors it to the floor. This hardware is designed primarily for use in locations where earthquakes are a concern. The feature includes a large steel brace or truss that bolts into the rear of the rack. It is hinged on the left side so it can swing out of the way for easy access to the rack drawers when necessary. The Ruggedized Rack Feature also includes hardware for bolting the rack to a concrete floor or a similar surface, and bolt-in steel filler panels for any unoccupied spaces in the rack. When a rack is bolted to the floor, the front and rear anti-tilt plates are not necessary. Racks ordered with FC#6080 are shipped without the anti-tilt plates. Instead, the base of the rack has an additional front trim panel. This panel is designed to accommodate a standard AC Power outlet.

(#6081) Front Trim Kit For 2.0 Meter Rack (Black)

(No Longer Available as of September 24, 2004)

The front trim kit consists of three steel parts that snap into the front of the rack at the left, right, and top edges. They are painted to match the overall rack color and designed to present an attractive, finished appearance. Each rack must be ordered with either a front door or a front trim kit, but not both.

(#6082) Front Trim Kit For 2.0 Meter Rack (White)

(No Longer Available as of December 31, 2001)

The front trim kit consists of three steel parts that snap into the front of the rack at the left, right, and top edges. They are painted to match the overall rack color and designed to present an attractive, finished appearance. Each rack must be ordered with either a front door or a front trim kit, but not both.

(#6083) Front Door For 2.0 Meter Rack (Black)

(No Longer Available as of December 3, 2001)

This feature provides an attractive full height rack door. The door is steel and has an extensive perforation pattern that allows ventilation and some visibility into the rack.

(#6084) Front Door For 2.0M OEM Rack (Black)

This feature provides an attractive full height rack door. The door is steel and has an extensive performation pattern that allows ventilation and some visibility into the rack.

(#6086) Suite Attach Kit For 2.0 Meter Rack (Black)

This feature allows a row of racks without side panels to be bolted together in a continuous suite, using the provided side to side rack connecting hardware. When multiple racks are joined in this way, cables can be easily run between racks without having to exit the continuous rack enclosure. A small gap is maintained between the two adjacent racks, which is filled by three matching steel trim pieces that snap into place on the front, top, and rear, between each rack. The trim pieces cover the space between each rack for an enhanced appearance and for additional protection of the equipment inside the racks. Side panels are needed only for the two end racks of the suite.

(#6087) Suite Attach Kit For 2.0 Meter Rack (White)

(No Longer Available as of December 31, 2001)

This feature allows a row of racks without side panels to be bolted together in a continuous suite, using the provided side to side rack connecting hardware. When multiple racks are joined in this way, cables can be easily run between racks without having to exit the continuous rack enclosure. A small gap is maintained between the two adjacent racks, which is filled by three matching steel trim pieces that snap into place on the front, top, and rear, between each rack. The trim pieces cover the space between each rack for an enhanced appearance and for additional protection of the equipment inside the racks. Side panels are needed only for the two end racks of the suite.

(#6089) Front Door for 2.0 Meter Rack (Sculptured Black)

(No Longer Available as of November 29, 2002)

This feature provides an attractive full height rack door. The door is black with sculptured accents. The door has an extensive perforation pattern that allows ventilation with some visibility into the rack.

(#6095) Power Cord for PDU to External I/O Device

This feature provides a line cord to power an external I/O device from the power distribution unit of the rack.

(#6098) Side Panel For 1.8 or 2.0 Meter Rack (Black)

This feature provides one rack side panel, which can be used on either the left side or the right side of the rack. A typical rack will require a quantity of two side panels, unless the Rack Suite Attachment feature is ordered. Rack side panels can be quickly installed or removed from the outside the rack, with no tools required.

(#6099) Side Panel For 1.8 Or 2.0 Meter Rack (White)

(No Longer Available as of December 27, 2002)

This feature provides one rack side panel, which can be used on either the left side or the right side of the rack. A typical rack will require a quantity of two side panels, unless the Rack Suite Attachment feature is ordered. Rack side panels can be quickly installed or removed from the outside the rack, with no tools required.

(#6171) Power Distribution Unit - Side Mount, Single Phase

(No Longer Available as of June 25, 2004)

This optional, additional, AC power distribution unit is available for systems requiring two separate AC power sources or for systems that require more than six power outlets. This unit is the same as the base unit (#9171). An additional line cord is provided with this unit. Do not increase the quantity of the line cord specify code

Note: First 3 Power Distribution Units (PDU) ordered with this feature number will be mounted in the back of the rack. Second 3 will be mounted horizontally in the rear of the rack, and will occupy 1U of rack space for each PDU.

(#6173) Power Distribution Unit - Side Mount, Two Of Three Phase

(No Longer Available as of June 25, 2004)

This optional, additional, AC power distribution unit is available for systems requiring two separate AC power sources or for systems that require more than six power outlets. This unit is the same as the base unit (#9173). An additional line cord is provided with this unit. Do not increase the quantity of the line cord specify code

Note: First 3 Power Distribution Units (PDU) ordered with this feature number will be mounted in the back of the rack. Second 3 will be mounted horizontally in the rear of the rack, and will occupy 1U of rack space for each PDU.

(#6238) - High-end Appearance Side Covers

This feature provides side covers designed to be used when the rack will contain a 9179-MHB.

(#6247) Thin Profile Front Trim Kit For 2.0 Meter Rack (Black)

(No Longer Available as of May 28, 2010)

The front trim kit consists of three steel parts that snap into the front of the rack at the left, right, and top edges. They are painted to match the overall rack color and designed to present an attractive, finished appearance. Each rack must be ordered with either a front door or a front trim kit, but not both.

(#6249) Acoustic Rack Doors, Front and Rear, 2.0 M

This feature provides front and rear rack doors designed to reduce acoustic sound levels in a general business environment.

(#6250) - High-end Appearance Front Door

This feature provides a front rack door with a field installed Power 780 logo designed to be used when the rack will contain a 9179-MHB.

(#6257) Rack Extender

The rack extender #6257 for the 7014-T42, provides the required cable management for the 7874-120 QLogic 9120 144-port DDR InfiniBand Fabric Director Switch, and the 7874-240 QLogic 9240 288-port DDR InfiniBand Fabric Director Switch. The rack extender is 20 inches deep.

(#6272) - 2.0m Rack Trim Kit

This feature provides a decorative trim kit for the front of feature number 0553 (19 inch 2.0m Rack).

(#6442) Power Cord, 7176/9176 PDU To Wall, 9800/9824 Equivalent

(No Longer Available as of June 23, 2006)

This feature provides the same power cord for a PDU that is provided when feature #9800 or #9824 is specified in the initial rack order.

(#6443) Power Cord, 7176/9176 PDU To Wall, 9801 Equivalent

(No Longer Available as of June 23, 2006)

This feature provides the same power cord for a PDU that is provided when feature #9801 is specified in the initial rack order.

(#6444) Power Cord, 7176/9176 PDU To Wall, 9822 Equivalent

(No Longer Available as of June 23, 2006)

This feature provides the same power cord for a PDU that is provided when feature #9822 is specified in the initial rack order.

(#6445) Power Cord, 7177/9177 PDU To Wall, 9823 Equivalent

(No Longer Available as of June 23, 2006)

This feature provides the same power cord for a PDU that is provided when feature #9823 is specified in the initial rack order.

(#6447) Power Cord, 7176/9176 PDU To Wall, 9826 Equivalent

(No Longer Available as of June 23, 2006)

This feature provides the same power cord for a PDU that is provided when feature #9826 is specified in the initial rack order.

(#6448) Power Cord, 7176/9176 PDU To Wall, 9835 Equivalent

(No Longer Available as of June 23, 2006)

This feature provides the same power cord for a PDU that is provided when feature #9835 is specified in the initial rack order.

(#6449) Power Cord, 7176/9176 PDU To Wall, 9986 Equivalent

(No Longer Available as of June 23, 2006)

This feature provides the same power cord for a PDU that is provided when feature #9986 is specified in the initial rack order.

(#6450) Power Cord, 7176/9176 PDU To Wall, 9987 Equivalent

(No Longer Available as of June 23, 2006)

This feature provides the same power cord for a PDU that is provided when feature #9987 is specified in the initial rack order.

(#6489) Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, IEC 309 3P+N+G 32A Plug

This power cord provides power to a #7188 or #9188 power distribution unit. It connects to a wall power outlet with an IEC 309 3P+N+G 32A plug.

(#6491) Power Cord, 7188/9188 PDU To Wall, 4.3M, 48A, IEC 309 P+N+G 63A Plug

This power cord provides power to a #7188 or #9188 power distribution unit. It connects to a wall power outlet with an IEC 309 P+N+G 63A plug.

(#6492) Power Cord, 7188/9188 PDU To Wall, 4.3M, 48A, IEC 309 2P+G 60APlug

This power cord provides power to a #7188 or #9188 power distribution unit. It connects to a wall power outlet with an IEC 309 2P+G 60A plug.

(#6546) White Rack Option, Factory Only

(No Longer Available as of December 10, 2004)

The standard color for racks is black. Racks ordered with this feature will be white.

(#6580) Rack Security Kit

This feature provides hardware that can be added to a rack to prevent unauthorized access. It includes keyed front and rear locks for the standard door latches. It also includes two sliding bars that mount inside the left and right rack side panels. The sliding bars are accessible when the rack rear door is open. They can be moved to a position that disables the external latches on the rack side panels, and prevents removal of the side panels.

(#6586) Modem Tray For 19-Inch Rack

This feature provides hardware for installing one or two modems in a 19-inch rack. The modem tray occupies 1U of rack space when it is mounted in the front of the rack. It provides a secure location in the rack for modems attached to 7315 Hardware Management Consoles.

(#6653) Power Cord, 7188/9188 PDU To Wall, 4.3M, 16A, IEC 309 3P+N+G 16A Plug

This power cord provides power to a #7188 or #9188 power distribution unit. It connects to a wall power outlet with an IEC 309 3P+N+G 16A plug.

(#6654) Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, NEMA L6-30 Plug

This power cord provides power to a #7188 or #9188 power distribution unit. It connects to a wall power outlet with a NEMA L6-30 plug.

(#6655) Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, RS 3750DP (Watertight) Plug

This power cord provides power to a #7188 or #9188 power distribution unit. It connects to a wall power outlet with an RS 3750DP (watertight) plug.

(#6656) Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, IEC 309 P+N+G 32A Plug

This power cord provides power to a #7188 or #9188 power distribution unit. It connects to a wall power outlet with an IEC 309 P+N+G 32A plug.

(#6657) Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, PDL Plug

This power cord provides power to a #7188 or #9188 power distribution unit. It connects to a wall power outlet with a PDL plug.

(#6658) Power Cord, 7188/9188 PDU To Wall, 4.3M, 24A, Korean Plug

This power cord provides power to a #7188 or #9188 power distribution unit. It connects to a wall power outlet with a Korean plug.

(#6667) - 4.3m (14-Ft) 3PH/32A Pwr Cd-Australia

#6667 is a 14-FT/4.3m 200-240V/24A power cord with a Type PDL plug which distributes power from a power source to a Power Distribution Unit.

(#6858) Rear Door Heat Exchanger for 7014-T42

This door replaces the standard rear door on the rack. Copper tubes attached to the rear door circulate chilled water, provided by the customer. The chilled water removes heat from the exhaust air being blown through the Servers and Attachments mounted in the Rack. The water lines in the door attach to the customer supplied secondary water loop using industry standard quick couplings.

(#6860) Mounting hardware kit

(No Longer Available as of June 23, 2006)

This feature delivers the required nut clips and screws to mount the 7048-120 or the 7048-270 into a rack.

(#7109) Intelligent PDU+, 1 EIA Unit, Universal, UTG0247 Connector

This feature is for an intelligent AC power distribution unit (PDU+) that will allow the user to monitor the amount of power being used by the devices that are plugged in to this PDU+. This AC power distribution unit provides twelve C13 power outlets. It receives power through a UTG0247 connector. It can be used for many different countries and applications by varying the PDU to Wall Power Cord, which must be ordered separately. Each PDU requires one PDU to Wall Power Cord. Supported power cords include the following features: #6489, #6491, #6492, #6653, #6654, #6655, #6656, #6657, and #6658.

(#7118) - Environmental Monitoring Probe

The Environmental Monitoring Probe (EMP) enables you to remotely monitor environmental conditions. Using a standard web browser, you can view the ambient temperature and humidity of the remote environment, as well as the status of two additional contact devices, such as a smoke detector or open-door sensor. The temperature/humidity probe plugs into a RJ45 connector an a PDU+. The EMP can be used with any Powerware UPS equipped with a 10/100 Mb ConnectUPS Web/SNMP Card (firmware V3.01 or higher). The EMP can be located up to 20m (65.6 feet) away.

(#7176) Power Distribution Unit - Side Mount, Single Phase, L6-30 Connector

(No Longer Available as of March 31, 2005)

This optional, additional, AC power distribution unit is available for systems requiring two separate AC power sources or for systems that require more than nine power outlets. This unit is the same as the base unit (#9176), and it provides nine C13 power outlets. An additional line cord is provided with this unit. Do not increase the quantity of the line cord specify code.

Note: First 3 Power Distribution Units (PDU) ordered with this feature number will be mounted vertically in the back of the rack. Any additional PDUs will be mounted horizontally in the rear of the rack, and will occupy 1U of rack space for each PDU.

(#7177) Power Distribution Unit - Side Mount, Single Phase, IEC-309 Connector

(No Longer Available as of March 31, 2005)

This optional, additional, AC power distribution unit is available for systems requiring two separate AC power sources or for systems that require more than nine power outlets. This unit is the same as the base unit (#9177), and it provides nine C13 power outlets. An additional line cord is provided with this unit. Do not increase the quantity of the line cord specify code.

Note: First 3 Power Distribution Units (PDU) ordered with this feature number will be mounted vertically in the back of the rack. Any additional PDUs will be mounted horizontally in the rear of the rack, and will occupy 1U of rack space for each PDU.

(#7178) Power Distribution Unit - Side Mount, Three Phase, IEC-309 Connector

(No Longer Available as of March 31, 2005)

This optional, additional, AC power distribution unit is available for systems requiring two separate AC power sources or for systems that require more than nine power outlets. This unit is the same as the base unit (#9178), and it provides nine C13 power outlets. An additional line cord is provided with this unit. Do not increase the quantity of the line cord specify code.

Note: First 3 Power Distribution Units (PDU) ordered with this feature number will be mounted vertically in the back of the rack. Any additional PDUs will be mounted horizontally in the rear of the rack, and will occupy 1U of rack space for each PDU.

(#7188) Power Distribution Unit - Side Mount, Universal, UTG0247 Connector

This optional, additional, AC power distribution unit is available for systems requiring two separate AC power sources or for systems that require more than twelve power outlets. This unit is the same as the base unit (#9188), and it provides twelve C13 power outlets.

(#9002) Field Integration Indicator, Ship Empty Rack

This feature on an order identifies that IBM manufacturing must ship the rack without installing any rack mount drawers. Exactly one feature selection from the set 9002 and 4651 through 4666 must be included on all initial rack orders. Feature 9002, when placed on an order will not affect the assembly of hardware items ordered as rack feature codes. When #9002 is included on the rack order, rack content specify codes should be included for any systems that will be installed in the rack after it leaves the factory.

(#9169) Order Routing Indicator - System Plant

This feature will be auto-selected by the Configurator Tool when required. Use of this feature will affect the routing of the order. Selection of this indicator will direct the order to a system plant for fulfillment.

(#9171) Power Distribution Unit Specify - Base/Side Mount, Single Phase

(No Longer Available as of June 25, 2004)

(#9173) Power Distribution Unit Specify - Base/Side Mount, Two Of Three Phase

(No Longer Available as of June 25, 2004)

(#9176) Power Distribution Unit Specify - Base/Side Mount, Single Phase, L6-30 Connector

(No Longer Available as of March 31, 2005)

This AC power distribution unit provides nine C13 power outlets.

(#9177) Power Distribution Unit Specify - Base/Side Mount, Single Phase, IEC-309 Connector

(No Longer Available as of March 31, 2005)

This AC power distribution unit provides nine C13 power outlets.

(#9178) Power Distribution Unit Specify - Base/Side Mount, Three Phase, IEC-309 Connector

(No Longer Available as of March 31, 2005)

This AC power distribution unit provides nine C13 power outlets.

(#9188) Power Distribution Unit Specify - Base/Side Mount, Universal, UTG0247 Connector

This AC power distribution unit provides twelve C13 power outlets. It receives power through a UTG0247 connector. It can be used for many different countries and applications by varying the PDU to Wall Power Cord, which must be ordered separately. Each PDU requires one PDU to Wall Power Cord. Supported power cords include the following features: #6489, #6491, #6492, #6653, #6654, #6655, #6656, #6657, and #6658.

(#9300) Language Group Specify - US English

English language group for nomenclature and standard publications.

(#9459) - PDU/PWR and Power Cord Redundancy Assurance

Feature 9459 facilitates matching up paired PDU, power supplies, and line cords for rack level redundancy. Including #9459 rectify the PDU, power supplies, and line cords? pairing for the configuration process and prevents manufacturing interruptions for improper quantities.

(#9703) Language Group Specify - French

French language group for Nomenclature and Standard Publications.

(#9704) Language Group Specify - German

German language group for Nomenclature and Standard Publications.

(#9705) Language Group Specify - Polish

Polish language group for Nomenclature and Standard Publications.

(#9707) Language Group Specify - Portuguese

Portuguese language group for Nomenclature and Standard Publications.

(#9708) Language Group Specify - Spanish

Spanish language group for Nomenclature and Standard Publications.

(#9711) Language Group Specify - Italian

Italian language group for Nomenclature and Standard Publications.

(#9712) Language Group Specify - Canadian French

Canadian French language group for Nomenclature and Standard Publications.

(#9714) Language Group Specify - Japanese

Japanese language group for Nomenclature and Standard Publications.

(#9716) Language Group Specify - Korean

Korean language group for Nomenclature and Standard Publications.

(#9719) Language Group Specify - Hungarian

Hungarian language group for Nomenclature and Standard Publications.

(#9720) Language Group Specify - Slovakian

Slovakian language group for Nomenclature and Standard Publications.

(#9721) Language Group Specify - Russian

Russian language group for nomenclature and standard publications.

(#9722) Language Group Specify - Simplified Chinese (PRC)

Simplified Chinese language group for nomenclature and standard publications.

(#9800) Power Cord Specify - United States/Canada

(No Longer Available as of March 31, 2005)

The following countries use the #9800 power cord to power the system unit and/or peripheral features requiring a power cord.

(#9801) Power Cord Specify - Raised Floor (US)

(No Longer Available as of March 31, 2005)

The #9801 power cord is used to power the system unit in a raised floor environment. When #9801 is ordered, the power cord includes a waterproof connector.

(#9822) Power Cord Specify - Australia

(No Longer Available as of March 31, 2005)

The following countries use power cord #9822 to power the system unit:

(#9823) Power Cord Specify - EMEA (PDU)

(No Longer Available as of March 31, 2005)

The following countries use power cord #9823 to power the system unit:

(#9824) Power Cord Specify - Japan and 60HZ AP

(No Longer Available as of March 31, 2005)

The following countries use power cord #9824 to power the system unit:

(#9826) Power Cord Specify - New Zealand

(No Longer Available as of March 31, 2005)

The following countries use power cord #9826 to power the system unit:

(#9835) Power Cord Specify - Korea (PDU)

(No Longer Available as of March 31, 2005)

(#9986) Power Cord Specify - Chicago (1.8M)(6 FT.)

(No Longer Available as of March 31, 2005)

The 6 foot #9986 power cord is used to power the system unit and/or peripheral features requiring a power cord.

(#9987) Power Cord Specify - Chicago (Raised Floor)

(No Longer Available as of March 31, 2005)

The #9987 power cord is used to power the system unit in a raised floor environment.

(#ECSC) - Custom Service Specify, Shenzhen, China

Having #ESCS on the order, will cause the order to be routed to Shenzhen and the machine to be internally routed to the CSC build area.

(#ECSM) - Custom Service Specify, Mexico

Having #ESCM on the order, will cause the order to be routed to Mexico and the machine to be internally routed to the CSC build area.

(#ECSP) - Custom Service Specify, Poughkeepsie, USA

Having #ECSP on the order, will cause the order to be routed to Poughkeepsie, USA and the machine to be internally routed to the CSC build area.

(#ECSS) - Integrated Solution Packing

This is a routing indicator for Solution packing.

(#EDAN) - Analytics Data Node Add-on

This feature is not supported by the configurator or by the PureFlex System.

(#EGSA) - IDEA Solution Specify

This feature indicates that this configuration is for IDEA Solution.

(#EGSB) - SOLUTION SPECIFY

This feature is use to identify Solution selection for adminstrative purposes within manufacturing to Faciliate processing.

(#EGSC) - GL2 SOLUTION SPEC 2TB DCS370E

Specify GL2 (12U) Solution with 7.2K HDD 2TB + DC3700E.

(#EGSD) - GL4 SOLUTION SPEC 2TB DCS370E

Specify GL4 (20U) Solution with 7.2K HDD 2TB + DCS3700E.

(#EGSE) - GL6 SOLUTION SPEC 2TB DCS370E

Specify GL6 (28U) Solution with 7.2K HDD 2TB + DCS3700E.

(#EGSF) - GL2 SOLUTION SPEC 4TB DCS370E

Specify GL2 (12U) Solution with 7.2K HDD 4TB + DCS3700E.

(#EGSG) - GL4 SOLUTION SPEC 4TB DCS370E

Specify GL4 (20U) Solution with 7.2K HDD 4TB + DCS3700E.

(#EGSH) - GL6 SOLUTION SPEC 4TB DCS370E

Specify GL6 (28U) Solution with 7.2K HDD 4TB + DCS3700E.

(#EGSJ) - GS1 SOLUTION SPEC 400GB #EL1S

Specify GS1 (6U) Solution with 400GB SSD + EXP24S SFF Gen2-bay Drawer.

(#EGSK) - GS1 SOLUTION SPEC 800GB #EL1S

Specify GS1 (6U) Solution with 800GB SSD and EXP24S SFF Gen2-bay Drawer.

(#EGSL) - GS2 SOLUTION SPEC 400GB #EL1S

Specify GS2 (8U) Solution with 400GB SSD and EXP24S SFF Gen2-bay Drawer.

(#EGSM) - GS2 SOLUTION SPEC 800GB #EL1S

Specify GS2 (8U) Solution with 800GB SSD and EXP24S SFF Gen2-bay Drawer.

(#EGSN) - GS2 SOLUTION SPEC 1.2TB #EL1S

Specify GS2 (8U) Solution with 10K 1.2TB HDD and EXP24S SFF Gen2-bay Drawer.

(#EGSP) - GS4 SOLUTION SPEC 400GB #EL1S

Specify GS4 (12U) Solution with 400GB SSD and EXP24S SFF Gen2-bay Drawer.

(#EGSQ) - GS4 SOLUTION SPEC 800GB #EL1S

Specify GS4 (12U) Solution with 800GB SSD and EXP24S SFF Gen2-bay Drawer.

(#EGSR) - GS4 SOLUTION SPEC 1.2TB #EL1S

Specify GS4 (12U) Solution with 10K 1.2TB HDD and EXP24S SFF Gen2-bay Drawer.

(#EGSS) - GS6 SOLUTION SPEC 1.2TB #EL1S

Specify GS6 (16U) Solution with 10K 1.2TB HDD and EXP24S SFF Gen2-bay Drawer.

(#ERLR) - Left/Right PDU Redundancy

This specify code will force an even number of PDUs onto the configuration and will alert Manufacturing to plug the PDU equipment in a left/right pattern. The L/R specify will be defaulted on all enterprise racks being configured. Default can be overriden during the configuration session.

(#ER00) - Custom Soln Center Services per PRPQ 8A2064

Routes system to the IBM Rochester Custom Solution Center for special services. Through PRPQ 8A2064 Customer is able to specify Ethernet Network and System cabling design. Customer is also able to provide input for manufacturing test. Other available services include customer ability to specify physical location of the systems, I/O drawers, IBM Ethernet Rack Switches and attached expansion drawers in the rack. Custom software and configuration of customer software per customer specification is available. The customer's input is collected and verified via i-Listed PRPQ 8A2064. Product safety rules must be met concerning weight distribution for shipping which may affect racking specification.

Final approval will be provided by the IBM Rochester Custom Solution Center via i-Listed PRPQ 8A2064.

(#ER02) - Rack Content Specify: 8408-E8D

Indicator or rack space utilization (5 EIA units)

(#ER03) - Rack Content Specify: 2076-224 - 2U

Indicator or rack space utilization

(#ER04) - Rack Content Specify: 2076-124 - 2U

Indicator or rack space utilization

(#ER07) - Rack Content Specify: 1611-16E 1EIA (BINGO)

Indicator or rack space utilization

(#ER08) - Rack Content Specify: 1455-24E

Indicator or rack space utilization

(#ER09) - Rack Content Specify: 1455-48E

Indicator or rack space utilization

(#ER0A) - Rack Content Specify: 1455-64C

Indicator or rack space utilization

(#ER0B) - Rack Content Specify: 1455-48T

Indicator for rack space utilization

(#ER0C) - Rack Content Specify: 1455-64F

Indicator for rack space utilization

(#ER0D) - Rack Content Specify: 9109-RMD

Indicator or rack space utilization (5 EIA units)

(#ER0E) - Rack Content Specify: 7316-TF4 -- 1 EIA

Indicator of rack space utilization.

(#ER0H) - Rack Content Specify: 8248-L4T

Indicator or rack space utilization (5 EIA units)

(#ER0J) - Rack Content Specify: 8412-EAD

Indicator or rack space utilization (4 EIA units).

(#ER0M) - Rack Content Specify for #EMX0 I/O Expansion Drawer

Allocates 4EIA unit space in Rack for the I/O Expansion Drawer (#EMX0).

(#ER0T) - Rack Content Specify 8286-41A/42A - 4EIA

Indicator of rack space utilization

(#ER0U) - Rack Content Specify: 8284-22A - 2EIA

Indicator of rack space utilization

(#ER0V) - Rack Content Specify: 8247-21L/22L - 2EIA

Indicator of rack space utilization

(#ER0Y) - Rack Content Specify: 8412-EAD

Indicator or rack space utilization

(#ER0Z) - Rack Content Specify: 8247-42L - 4EIA

Indicator of rack space utilization

(#ER10) Rack Content Specify first enclosure: 9119-MHE, 9119-MME - 7 EIA

Rack content specify for first enclosure - 7 EIA. Supports 9119-MHE and 9119-MME.

(#ER11) Rack Content Specify second enclosure: 9119-MHE, 9119-MME - 12 EIA

Rack content specify for second enclosure - 12 EIA. Supports 9119-MHE and 9119-MME.

(#ER12) Rack Content Specify third enclosure: 9119-MHE, 9119-MME - 17 EIA

Rack content specify for third enclosure - 17 EIA. Supports 9119-MHE and 9119-MME.

(#ER13) Rack Content Specify fourth enclosure: 9119-MHE, 9119-MME - 22 EIA

Rack content specify for fourth enclosure - 22 EIA. Supports 9119-MHE and 9119-MME.

(#ER14) Rack Content Specify 1U Horizontal PDU: 9119-MHE, 9119-MME - 1 EIA

Rack content specify for 1U Horizontal PDU - 1 EIA. Supports 9119-MHE and 9119-MME.

(#ER15) Rack Content Specify reserve 5U rack space: 9119-MHE, 9119-MME

Rack content indicator for virtual enclosure - Reserve 5U rack space - 5 EIA. Supports 9119-MHE and 9119-MME.

(#ER18) - Rack Content Specify: 8247-21L - 2EIA

Indicator of rack space utilization

(#ER19) - RACK SPECIFY FC EMX0

Indicator that reserve adjacent 4EIA rack space for the I/O Expansion Drawer feature EMX0.

(#ER1B) Rack Content Specify: Reserve 1U Rack Space at Bottom of Rack

Indicator or rack space utilization

(#ER1F) - FlashSystem 9840/9843 - 2 E1A

Indicator for 2 EIA rack space utilization for FlashSystem Drawer

(#ER1T) Rack Content Specify: Reserve 1U Rack Space at Top of Rack

Indicator or rack space utilization

(#ER2B) Rack Content Specify: Reserve 2U Rack Space at Bottom of Rack

Indicator or rack space utilization

(#ER2T) - Rack Content Specify: Reserve 2U Rack Space at Top of Rack

Indicator or rack space utilization

(#ERG0) - Rack Rear Extension

Extends the rear of a 2.0M enterprise rack (7014-T42) eigth inches or 20.3 cm. The extra depth provides extra space for cable management helping to keep the center of the rack more open for airflow and access to the rear of the equipment mounted in the rack. This rear extension does not increase or decrease the rack's 42 EIA (42U) vertical size. The extension does increase the floor footprint.

(#ERG7) Front Door for Power 770 & 780 2.0 Meter Rack (High Perforation)

This feature provides an attractive black full height rack door. The door is steel, with a perforated flat front surface. The perforation pattern extends from the bottom to the top of the door to enhance ventilation and provide some visibility into the rack.

(#ESC0) - S&H - No Charge

No charge shipping and handling.

(#ESC1) - Rack S&H-a

Feature exchanges

Not available
Back to topBack to top
 
Accessories

None

Customer replacement parts

None
Back to topBack to top
 
Machine elements

None
Back to topBack to top
 