IBM 9910 UPSs for IBM eServer iSeries and pSeries safeguard your equipment and data from power problems

IBM United States Hardware Announcement 104-126
April 20, 2004

 ENUS104-126.PDF (70KB)

Table of contents   Document options  
At a glance Services
Overview Technical information
Key prerequisites Input/Output (I/O) configuration
Planned availability dates Terms and conditions
Description Prices
Accessibility by people with disabilities Order now
Publications  
 
Printable version

 
At a glance

The IBM 9910 UPSs offer you:

  • Models that are tested and approved by IBM
  • An extended warranty supported by IBM
  • A premium service package (including battery)
  • Enhanced conditioning of utility power and battery backup
  • Installation and startup by Powerware for Models P93 and P95

For ordering, contact:

Your IBM representative, an IBM Business Partner, or IBM Americas Call Centers at 800-IBM-CALL (Reference: YE001).
 
Back to top
 

Overview

To meet the changing power protection needs of IBM servers, IBM Global Services has selected new Uninterruptible Power Systems (UPSs) from Powerware.

The new IBM 9910 UPS solution, compatible with the power requirements for RS/6000®, IBM eServer pSeries®, AS/400®, and iSeries™ servers, has passed IBM's rigorous testing procedures and is intended to provide a convenient, single source for purchase and protection of IBM servers. All 9910 UPSs include a premium warranty package that is designed to enhance the potential for a return on investment over other UPSs available on the market today. In addition, the IBM warranty:

  • Extends coverage of the UPS (refer to the specific product warranty period)
  • Provides remote problem determination and next-day exchange (if available) by the UPS manufacturer (when necessary)
  • Offers a single point of contact through the IBM Call Center

IBM offers the following Powerware products for iSeries and pSeries servers:

  • PW9330-20 (P93) (three-phase model) incorporates a high level of service, design, and performance to help keep iSeries and pSeries servers working virtually without interruption.
  • PW9305-30 (P95) (three-phase model) provides advanced, feature-rich power management for iSeries and pSeries servers.
  • P93 includes a one-year ProActive Service Plan. With the ProActive Service Plan, you receive service above the standard warranty.
  • Extended Battery Module (EBM) (#6635) provides extended runtime (autonomy) for P93.
  • EBM (#6636) provides extended runtime (autonomy) for P95.
  • True online double-conversion three-phase power protection.
  • ConnectUPS X-Slot Web/simple network management protocol (SNMP)/xHub option provides realtime monitoring of power conditions with Secure Socket Layer (SSL).
  • Powerware 9125 3 kVA (P30) and 6 kVA (P64) provide true online, double-conversion UPSs with a versatile design that allows the UPS to be rack-mounted or installed as a tower.

 
Back to top
 
Key prerequisites

The key prerequisites consist of the operating system and the selected applications that are required for your business.


 
Back to top
 

Planned availability dates
  • April 20, 2004: Models P93, P95, and P64
  • July 20, 2004: Model P30

 
Back to top
 
Description

Powerware Uninterruptible Power Systems

The Powerware 9330 Model 20 (P93) integrates advanced technology, software, and service capabilities into a single module capable of supporting critical servers, ISPs, telecommunications, or process control equipment. By incorporating DC Expert Plus Built-in Battery Monitoring and advanced communications, the P93 offers one of the highest levels of reliability for critical systems and one of the lowest overall cost of ownership for a double-conversion online UPS in the 20 kVA range. The P93 includes a one-year ProActive Service Plan. With the ProActive Service Plan, you receive service above the standard warranty. Additional years of ProActive Service Plan can be ordered using feature numbers 7001 or 7002. To ensure all aspects of installation planning are taken into consideration, optional feature number 7005 can be ordered, which provides a site survey by an IBM installation planning representative.

The Powerware 9305 Model 30 (P95) is designed to provide optimum protection with its double conversion online design, advanced communications capabilities, Advance Management (ABM) technology for doubled battery service life, and high reliability with Hot Sync parallel redundancy system. Specifically designed for use in server rooms or server farms for centralized power protection, the P95 offers the flexibility and some of the highest levels of power protection to critical IT equipment. The P95 includes a one-year ProActive Service Plan. With the ProActive Service Plan, you receive service above the standard warranty.

The 9910-P30 (Powerware 9125 3000 VA 208-240 V ac single phase) UPS protects up to 2100 watts and the 9910-P64 (Powerware 9125 6000 VA 208-2 40 V ac single phase) UPS protects equipment up to 4200 watts. These true online, double-conversion UPSs feature ABM technology which doubles battery service life, load segments for schedule shutdowns (not available on P64) and extended runtimes, and a versatile design that allows the UPS to be mounted as a rack or a tower. Optional Extended Battery Modules (EBMs) extends battery runtimes, and the ConnectUPS Web/SNMP/xHub card adapter expands control and monitoring of UPS and network devices.

To accommodate increased requests for rack UPS solutions for iSeries models, the 9910 Model P33, previously announced in Hardware announcement 101-227 , dated August 14, 2001, will be made available for iSeries clients. Powerware offers the AS/400 Bundled X-Slot Relay Card (#2936) and a 25-foot (7.6 meters) AS/400 interface cable to provide a comprehensive solution for iSeries rack clients.
 
Back to top
 

Accessibility by people with disabilities

For hardware offerings, the following features support use by people with disabilities:

  • Controls and latches are operable with one hand and minimal dexterity.
  • Keys are discernible by touch without activating them.
  • Ports and connectors support connection of industry-standard devices.

Additional information

All offers are subject to availability. IBM reserves the right to alter product offerings and specifications at any time without notice. IBM is not responsible for photographic or typographic errors.

IBM makes no representation or warranty regarding third-party products or services.

Trademarks

 
iSeries is a trademark of International Business Machines Corporation in the United States or other countries or both.
 
RS/6000, AS/400, the e-business logo, and pSeries are registered trademarks of International Business Machines Corporation in the United States or other countries or both.
 
Other company, product, and service names may be trademarks or service marks of others.

 
Back to top
 
Publications

Product-specific publications are shipped with the products. Additional copies are available from the associated UPS supplier.
 
Back to top
 

Services

Integrated technology services (IBM Global Services)

IBM services range from business consulting, outsourcing, hosting services, applications, and other technology management.

IBM technology services help you learn about, plan, install, manage, or optimize your IT infrastructure for e-business. We can help you integrate your high-speed networks, storage systems, application servers, wireless protocols, and an array of platforms, middleware, and communications software for IBM and many non-IBM offerings. IBM is your one-stop shop for IT support needs.

Visit the appropriate link below for details on services available dependant on the brand the product belongs to.

For details on education offerings related to the products listed, visit

Select your country; then select the product as the category.

For more details on IBM Global Services capabilities, contact your IBM representative, or visit

Your IBM representative can help you determine availability of standard and customized services.
 
Back to top
 

Technical information

Specified operating environment

Physical specifications: Physical specifications are subject to change. More detailed specifications can be obtained from your IBM representative or at the following Web site

Model P30 (3000 VA, 2100 Watts)

  • Width: 43.18 cm (17.0 in)
  • Depth: 60.71 cm (23.9 in)
  • Height: 8.89 cm (3.5 in), 2U
  • Weight: 36.97 kg (81.5 lb)

Feature 6640 (Extended Battery Module for P30)

  • Width: 43.18 cm (17.0 in)
  • Depth: 62.87 cm (24.75 in)
  • Height: 8.89 cm (3.5 in), 2U
  • Weight: 42.18 kg (93 lb)

Feature 6570 (PowerPass Distribution Module for P30)

  • Width: 43.18 cm (17.0 in)
  • Depth: 62.87cm (24.75 in)
  • Height: 8.89 cm (3.5 in), 2U
  • Weight: 22.68 kg (50 lb)

Model P64 (6000 VA, 4200 Watts)

  • Width: 43.18 cm (17.0 in)
  • Depth: 63.35 cm (24.94 in)
  • Height: 21.92 cm (8.63 in), 5U
  • Weight: 93.44 kg (206 lb)

Feature 6641 (Extended Battery Module for P64)

  • Width: 43.18 cm (17.0 in)
  • Depth: 62.87 cm (24.75 in)
  • Height: 13.35 cm (5.25 in), 3U
  • Weight: 76.66 kg (169 lb)

Feature 6571 (PowerPass Distribution Module for P64)

  • Width: 43.18 cm (17.0 in)
  • Depth: 62.87 cm (24.75 in)
  • Height: 13.34 cm (5.25 in), 3U
  • Weight: 48.08 kg (106 lb)

Feature 6572 (PowerPass Distribution Module for P64)

  • Width: 43.18 cm (17.0 in)
  • Depth: 62.87cm (24.75 in)
  • Height: 13.34 cm (5.25 in), 3U
  • Weight: 48.08 kg (106 lb)

Feature 2936 (ConnectUPS Relay Card and Interface for P30, P33, P64, and P93)

  • Width: inserts into X-Slot
  • Depth: inserts into X-Slot
  • Height: inserts into X-Slot
  • Weight: 1 lb

Feature 2938

(Environmental Monitoring Probe for Feature Numbers 2934 and 2935)

  • Width: 3.76 cm (1.48 in)
  • Depth: 5.76 cm (2.26 in)
  • Height: 2.93 cm (1.15 in)
  • Weight: 34 g (1.19 oz)

UPS Model P93 (20 kVA) consists of two cabinets

UPS (Power, electronics, and integral battery) cabinet

  • Width: 56 cm (22 in)
  • Depth: 79 cm (31 in)
  • Height: 114 cm (45 in)
  • Weight: 437.7 kg (965 lb)

Options (External maintenance bypass, output circuit breakers, and power distribution) cabinet

  • Width: 56 cm (22 in)
  • Depth: 97 cm (38 in)
  • Height: 114 cm (45 in)
  • Weight: 90 kg (200 lb)

Feature 6635 (Extended battery cabinet for P93)

  • Width: 52 cm (17 in)
  • Depth: 79 cm (31 in)
  • Height: 114 cm (45 in)
  • Weight: 272 kg (600 lb)

To verify the ability to be installed and serviced in non-IBM industry-standard racks, review the installation planning information for any product-specific installation requirements.
 
Back to top
 

Input/Output (I/O) configuration

                                               Input Plug/
Model          Output Receptacles              Connector
 
P30            (4 ea) IEC-320-C13 10A,         IEC-320-C20 16A
               (1 ea) IEC-320-C19 16A
P64            (1 ea) L6-30R                   L6-30AR
6570           (2 ea) 5-15,(4 ea) 6-20         IEC-320-C20 16A
               (2 ea) L6-15
6571           (2 ea) 5-15,(4 ea) 6-20         L6-30AR
 
               (2 ea) L6-15, L6-30
6572           (8 ea) IEC-320 C13 10A,         L6-30AR
               (4 ea) IEC-320 C19 16A,
               (1 ea) IEC309 P+N+G 32A
               3 pin
P93            (2 ea) 60A IEC309               Wired to Electric
               460R9W                          Service Panel

Operating environment

Model P30

  • Operating temperature: 0°C to 40°C (32°F to 104°C)
  • Storage temperature: 0°C to 25°C (32°F to 77°C)
  • Relative humidity: 0% to 90%, non-condensing
  • Audible noise at one meter: Less than 45 dBA (on utility); less than 50 dBA (on battery)
  • Input voltage: Autosensing to nominal voltage of 208, 220, 230, or 240 V single phase
  • Input voltage range: 160-288 V single phase (without using batteries)
  • Output voltage: 120/208 (with 6570 PPDM), 208, 220, 230, or 240 V single phase

Model P64

  • Operating temperature: 0°C to 40°C (32°F to 104°C)
  • Storage temperature: 0°C to 25°C (32°F to 77°C)
  • Relative humidity: 5% to 90%, non-condensing
  • Audible noise at one meter: Less than 45 dBA (on utility); less than 50 dBA (on battery)
  • Input voltage: Autosensing to nominal voltage of 208, 220, 230, or 240 V single phase
  • Input voltage range: 160-288 V single phase (without using batteries)
  • Output voltage: 120/208 (with 6571 PPDM), 208, 220, 230, or 240 V single phase

Model P93

  • Operating temperature: 0°C to +40°C (32°F to 104°C)
  • Storage temperature: -20 to +70°C (-4°F to 140°F)
  • Relative humidity: 95% maximum, non-condensing
  • Audible noise at one meter: Less than 60 dBA
  • Operation elevation: 1500 m (5000 ft) at 40 C without derating
  • Input voltage: 120/208 V ac, 60 Hz, 3-phase + GND (rectifier); 208Y/120 V ac, 60 Hz, 3-phase + N + GND (Bypass)
  • Output voltage: 208Y/120, 60 Hz
  • Input voltage range: -15%, +10%

Software requirements

The 9910 UPS solutions come with the Powerware Software Suite CD-ROM containing FREE LanSafe and NetWatch software. Powerware Extensions for IBM Director are FREE and downloadable from the Web.

With comprehensive Network Power Management and 9910 UPS solutions from Powerware, you can realize key benefits of:

  • Realtime information on network-wide power quality and events which affect system availability
  • Control of power connected to individual or network devices
  • Continuous clean power to each device
  • Automatic and graceful shutdown of individual or network devices during extended power outages
  • Monitoring to analyze and diagnose network problems

Software to application matrix

Powerware software

                                                    Powerware
                      LanSafe                       Extension for
Application           V5           NetWatch         IBM Director
 
single pSeries        X
 (serial/TTY)
 non-LPAR
single pSeries        X(1)         X(1)
 (network)
 non-LPAR
single pSeries                     X(1)
 (LPAR)
multiple pSeries      X            X(1)
 (non-LPAR)
multiple pSeries                   X(1)
 (LPAR)
IBM Director                                        X(1)
 network device

Note: UPS for iSeries applications utilize OS/400® UPS monitoring functions

1
Corequisite feature numbers 2934 or 2935 ConnectUPS Web/SNMP network card.

Application comparison matrix

Software           Monitoring      Shutdown      GUI      E-mail
 
LanSafe            Y               Y             Y        Y
NetWatch           --              Y             --       N/N
 ConnectUPS
Web/SNMP           Y(2)            Y(3)          Y        Y/Y
 Card

UPS                         SSL/SSH                Ambient
Application                 Security               Temp/Humidity
 
LanSafe                     N/N                    N/N
NetWatch                    N/N                    N/N
 ConnectUPS
Web/SNMP Card               Y/Y                    Y(4)/Y(4)
2
Via Web Browser, LanSafe or Network Management System
3
In conjunction with NetWatch software
4
With optional FN 2938 EMP (Environmental Monitoring Probe) device attached.

The following LanSafe V5 operating systems are supported:

  • Linux Redhat V7.1, 7.2, 7.3, 8.0, 9.0
  • Linux SuSE V7.2
  • AIX® V4.1, 4.3.2, 4.3.3, 5.1, 5.2

The following NetWatch operating systems are supported:

  • IBM AIX V4.x, 5.x (PowerPC®)
  • Linux kernel V2.0 and higher (Intel™)

Additional supported operating systems and information about Powerware UPS, network, enterprise-wide monitoring and control software can be found at the following Web site

Planning information

Customer responsibilities: The 9910 UPS Models P30 and P64 are designated as customer set-up, which includes installation of two battery trays for the P64, each weighing 59 pounds (27 kg). If Models P30, P64, and features 6640 and 6641 are not ordered with the iSeries and pSeries rack, the client will be responsible for the installation of external cables, UPS module, and battery module. Clients who request IBM service personnel to perform these activities are subject to a charge. Client responsibilities for the P30 and P64 include:

  • Adequate site and system planning, and preparation
  • Receipt, unpacking, and placement of the system unit
  • Ordering, installing, and maintaining cables with associated parts for attaching to the pSeries model
  • Using and following the problem determination procedures in the operators guide
  • Installing UPS management software and setting UPS run-time parameters

The 9910 UPS Models P93 and P95 are designated as a combination Powerware installation and customer set-up. If feature number 6635 and/or 6636 is not ordered with the UPS (P93, P95), the client will be responsible for installation of these features. Clients who request IBM service personnel to perform these activities are subject to a charge. Client responsibilities for Models P93 and P95 include:

  • Adequate site and system planning and preparation with support from IBM and Powerware personnel
  • Receipt, positioning of the system unit at ground level to installation area
  • Ordering, installing, and maintaining cables with associated parts for attaching to the pSeries model
  • Using and following the problem determination procedures in the operators guide
  • Installing UPS management software and setting UPS run-time parameters

Cable orders

9910 Model P93

Power (electrical) cables

The input (mains) power to the 9910-P93 is hardwired by a Powerware installation contractor into a client-provided power distribution panel. Refer to the Machine installation section for installation service description.

Two types of output power distribution connection outlets (receptacles) are available, feature numbers 9880 and 9881. The base P93 includes one feature number 9880 which contains two 60A, 3-phase, 4-wire IEC309 460R9W connectors with appropriate circuit breakers and connectors. Each connector shall be on a maximum 50-foot cord. This feature number supports dual-redundant power cords of the base processor frame or CPU. The maximum quantity of feature number 9880 is one.

Optional output power distribution connections are available with feature number 9881. Each feature number 9881 contains three 15 A to 30 A NEMA non or locking receptacle with appropriate circuit breakers and connectors (power cord). Each connector shall be on maximum 50-foot cord and wired into the Options Cabinet output distribution panel. The description of the Options Cabinet is as follows:

  • Option Cabinet 20 kVA capacity, single feed, 208/208, maintenance bypass, and 42-pole panel with output connection housing.
  • Valid receptacle types are: NEMA; 5-15R2, 5-20R2, L5-15R, L5-20R, 30R, L5-30R, 6-15R, L6-15R, 6-20R, L6-20R; and, L6-30R.

    Note: 15 A and 20 A non-locking, low voltage (5-15R2 and 5-20R2) are duplex (two receptacles).

  • The minimum quantity of feature number 9881 is zero.
  • The maximum quantity of feature number 9881 is six.
  • Feature numbers 9880 and 9881 will be installed to the P93 configuration at time of UPS installation.
  • The IEC and NEMA plug types used in feature numbers 9880 and 9881 correspond to IBM plug types.
  • Refer to the following:

              IEC/NEMA Type                   IBM Plug Type
     
              IEC309 460R9W                   NA
              5-15                            4
              5-20                            30
              L5-15                           7
              L5-20                           8
              L5-30                           9
              6-15                            5
              6-20                            29
              L6-15                           10
              L6-20                           11
              L6-30                           12
    

NA = Not applicable

If the plug type selected for the equipment to be protected by the 9910-P93 is not contained in this table, change the plug type on the equipment to match plug types available with feature numbers 9880 or 9881.

Feature 6635 (External Battery Module)

The input power to the 6635 is DC and is provided by the P93. If installation of 6635 is concurrent to P93, installation of the DC cable is hardwired by a Powerware installation contractor at installation. Feature number 6635 is a line-up-and-match cabinet connected to P93 cabinet. If installation of 6635 is non-concurrent or a Miscellaneous Equipment Specification (MES), installation is the responsibility of the client.

Communications cables

One iSeries (AS/400®) to UPS interface cable (25 ft/7.6 m length) and one server to UPS serial TTY interface cable DB9 to DB9 (6 ft/1.8 m length) are included with the P93 for iSeries and pSeries orders. To use the Remote Notify capability of the P93, the provided serial port will be connected to a provided modem. The modem will require a client-supplied dedicated (analog) telephone line.

There are two unused communications ports available for optional communications cards (#2933, #2934, or #2936).

The optional feature number 2933 (ConnectUPS MultiServer Card) includes three server to UPS serial TTY interface cables DB9 to DB9 (6 ft/1.8 m length).

Note: This feature number is used to serially communicate with two or three servers.

The optional feature number 2934 (ConnectUPS Web/SNMP/xHub Card) includes one UPS to Web Card configuration cable RJ45 to DB9M (6 ft/1.8 m length).

Note: This feature number is required if using LPAR on pSeries.

The optional feature number 2936 (ConnectUPS Relay Card and Interface Cable) includes iSeries (AS/400) to UPS interface cable (25 ft/7.6 m length).

The optional feature number 2938 (ConnectUPS EMP) includes one CAT5 cable (6 ft/1.8 m length). Corequisite is feature number 2934. Min: 0, Max: 1 feature number 2938 per feature number 2934.

9910 Model P95

Power (electrical) cables

The input (mains) power to the 9910-P95 is hardwired by a Powerware installation contractor into a client-provided mains distribution panel. Refer to the Machine installation section for installation service description.

Three output power distribution connection outlets (receptacles) are available, feature numbers 9883, 9884, and 9885.

Cabling Option A (#9884) includes one 32A 3-phase commando 5-hole (TPN&E) 415 V socket (floor mountable, angled as per RS 352-2581) attached to 4 mm two 5-core steel wire armoured (SWA), low smoke and fume (LSF)-type mains cable, 12 meters long; and one unconnected 32A 3-phase commando 5-hole (TPN&E) 415 V plug (straight free plug as per RS 352-2294). Presentation: Cable to be pre-terminated to socket. Plug to be married to socket connector.

Cabling Option B (#9885) includes three 32A 1-phase commando 3-hole (SPN&E) 240 V socket (floor mountable, angled as per RS 352-2547) each attached to 4 mm two 3-core SWA, LSF-type mains cable, 12 meters long; and three unconnected 32A 1-phase commando 3-hole (SPN&E) 240 V plugs (straight free plug as per RS 352-2244). Presentation: Cable to be pre-terminated to socket. Plug to be married to socket connector.

Cabling Option C (#9883) includes three 16A 1-phase commando 3-hole (SPN&E) 240 V socket (floor mountable, angled as per RS 352-2531) each attached to 4 mm two 3-core SWA, LSF-type mains cable, 12 meters long; and three unconnected 16A 1-phase commando 3-hole (SPN&E) 240 V plugs (straight free plug as per RS 352-2238). Presentation: Cable to be pre-terminated to socket.

Feature numbers 9883, 9884, and 9885 will be installed to the P95 configuration at time of UPS installation.

Feature 6636 (External Battery Module)

The input power to the 6636 is DC and is provided by the P95. If installation of 6636 is concurrent to P95, installation of the DC cable is hardwired by a Powerware installation contractor at INSTALLATION. Feature number 6636 is a line-up-and-match cabinet connected to P95 cabinet. If installation of 6636 is non-concurrent or a MES, installation is the responsibility of the client.

Communications cables

One iSeries (AS/400) to UPS interface cable (15 ft/5 m length) and one server to UPS serial TTY interface cable DB9 to DB9 (6 ft/2 m length) are included with the P95 for iSeries and pSeries orders. The optional feature number 2935 (ConnectUPS E (external) Web/SNMP adapter) includes one UPS to ConnectUPS Adapter configuration cable 9PinM (P95) to 25PinF (ConnectUPS) (6 ft/1.8 m length).

Note: This feature number is required if using LPAR pSeries.

The optional feature number 2938 (ConnectUPS Environmental Monitoring Probe (EMP)) includes one CAT5 cable (6 ft/1.8 m length). Corequisite is feature number 2935. Min: 0, Max: 1 feature number 2938 per feature number 2935.

9910 Model P30

Power (electrical) cables

The input (mains) power connection to the 9910-P30 is an IEC-320-C20 (16A) connector. The input (mains) power cord from the UPS to the utility (mains) is determined based upon country or locality. Refer to the following 9910-P30 input power cord table:

Feature        Plug
number         type        Plug description          Length
 
9860           11          NEMA L6-20                14 ft/4.4 m
9861           11          NEMA L6-20                 6 ft/1.8 m
9866           18          CEE7 VII                  14 ft/4.4 m
9867           22          SABS 164                  14 ft/4.4 m
9868           25          CEI 23-16                 14 ft/4.4 m
9871           46          IEC309 (P+N+G) 16A        14 ft/4.4 m
9872           32          SII 32-1971               14 ft/4.4 m
9874           54          SAA(R)-AS 3112            14 ft/4.4 m
9875           64          IEC 60083-A5              14 ft/4.4 m

When the 9910-P30 is employed in a rack installation (iSeries or pSeries) or in a tower configuration for world trade countries, the P30 output (receptacle) configuration is four IEC-320-C13 (10A) and one IEC-320-C19 (16A). The 9910-P30 also includes five (5) output power cable consisting of four IEC-320-C13 to C14 (6 ft/1.8 m length) and one IEC-320-C19 to C20 (14 ft/4.4 m length). These power cables are located in the "Power Cord Kit" carton, IBM feature number 9830. A maximum of one feature number 9830 is supported.

When the 9910-P30 is employed in a tower configuration in NEMA-type countries, the P30 will include one NEMA-type PowerPass Distribution Module (PPDM) IBM feature number 6570, which contains the following output (receptacle) connections. IBM plug types supported are referenced.

Feature 6570 output connection table

                                                       IBM plug
                            Qty                        types
NEMA type                   provided                   supported
 
5-15/5-2                    2                          4
6-15/6-20                   4                          5/29
L6-15                       2                          10

If the plug type selected for the equipment to be protected by the 9910-P30 is not contained in this table, change the plug type on the equipment to match plug types available with feature number 6570.

Power electrical cable installation diagrams are at the following Web sites:

NEMA countries

IEC countries

Feature 6640 (External Battery Module)

The input power to the 6640 is DC and is provided by the P30. Connection of the 6640 DC cable (Anderson-type DC connector) is the responsibility of the client and is performed at installation. Feature number 6640 is a line-up-and-match cabinet connected to P30 cabinet.

Communications cables

One server to UPS serial TTY interface cable DB9M to DB9F (6 ft/1.8 m length) is included with the P30 (contained in the P30 Accessory Kit carton) for all (iSeries and pSeries) orders. The P30 includes a single serial port (DB9) contained on a removable ConnectUPS X-Slot interface card. Optional communications features (#2933, #2934, and #2936) will replace this single port serial card. A maximum of one feature number 2933, or 2934, or 2936 is supported.

The optional feature number 2933 (ConnectUPS MultiServer Card) includes three server UPS serial TTY interface cables DB9 to DB9 (6 ft/1.8 m length). Min: 0 , Max: 1 per P30.

Note: This feature number is used to serially communicate with two or three servers.

The optional feature number 2934 (ConnectUPS Web/SNMP/xHub Card) includes one UPS to Web Card configuration cable RJ45 to DB9M (6 ft/1.8 m length).

Note: This is required if using LPAR on pSeries. Min: 0, Max: 1 per P30.

The optional feature number 2936 (ConnectUPS Relay Card) includes one iSeries (AS/400) to UPS interface cable (25 ft/7.6 m length). This feature number is included with iSeries orders. Min: 0, Max: 1 per P30.

The optional feature number 2938 (ConnectUPS Environmental Monitoring Probe (EMP)) includes one CAT5 cable (6 ft/1.8 m length). Corequisite is feature number 2934. Min: 0, Max: 1 feature number 2938 per feature number 2934.

9910 Model P64

Power (electrical) cables

The input (mains) power connection to the 9910-P64 is a NEMA L6-30AR (30A) connector. The input (mains) power cord from the UPS to the utility (mains) is determined based upon country or locality. Refer to the following 9910-P64 input power cord table:

Feature        Plug
number         type        Plug description          Length
 
1420           12          NEMA L6-30                14 ft/4.4 m
1421           12          NEMA L6-30                 6 ft/1.8 m
1422           40          RS 3750                    6 ft/1.8 m
1423           40          RS 3750                   14 ft/4.4 m
1424           46          IEC309 (P+N+G) 32A        14 ft/4.4 m
1425           KP          KP                        14 ft/4.4 m
1426           PDL         PDL                       14 ft/4.4 m
1427           PDL         PDL-NZ                    14 ft/4.4 m

When the P64 is used as a RACK model and the PDU is feature number 5160, 7176, or 9176 (NEMA type), none of the above power cables are needed. The power cord shipped for the PDU is used from the P64 to the wall (mains). Feature number 2970 is used to the NEMA PDU to the output receptacle of the P64. Feature number 2970 is one power NEMA L6-30P to NEMA L6-30R (6 ft./1.8 m length).

When the P64 is used as a RACK model and the PDU is feature number 5161, 7177, or 8177 (IEC type), the above cables are needed. Feature number 2971 is used to connect the IEC PDU to the output receptacle of the P64. Feature number 2971 is one power cord, NEMA L6-30P to IEC309 (P+N+G) 32A receptacle (6 ft/1.8 m length).

Output PDU to UPS power cord table

Feature              Plug          Receptacle
number               type          type               Length
 
2970 for PDU         NEMA          NEMA L6-30         6 ft/1.8 m
 5160, 7176           L6-30
 or 9176
2971 for PDU         NEMA          IEC309             6 ft/1.8 m
 5161, 7177           L6-30         (P+N+G)
 or 8177                            32A

When the 9910-P64 is employed in a tower configuration in NEMA-type countries, the P64 will include one NEMA-type PowerPass Distribution Module (PPDM) IBM feature number 6571, which contains output (receptacle) connections described in the feature number 6571 output connection table. IBM plug types supported are referenced.

Feature number 6571 output connection table

                                                       IBM plug
                            Qty                        types
NEMA type                   provided                   supported
 
5-15/5-20                   2                          4
6-15/6-20                   4                          5/29
L6-15                       2                          10
L6-30                       1                          12

If the plug type selected for the equipment to be protected by the 9910-P4 is not contained in this table, change the plug type on the equipment to match plug types available with feature number 6571.

When the 9910-P64 is employed in a tower configuration in world trade countries, the P64 will include one IEC-type PPDM IBM feature number 6572, which contains output (receptacle) connections described in the feature number 6572 output connection table. IBM plug types supported are referenced.

This 9910-P64 configuration includes two sets of five output power cables consisting of: four (4) IEC-320-C13 to C14 (6 ft/1.8 m length) and one IEC-320-C19 to C20 (14 ft/4.4 m length). These power cables are located in the "Power Cord Kit" cartons, IBM feature number 9830. A maximum of two feature number 9830s are supported. In addition to the two feature number 9830s, feature number 6572 contains two IEC-320-C19 to C20 (14 ft/4.4 m length) power cords and are located in the 6572 carton.

Feature 6572 output (receptacle) connection table

                                                       IBM plug
                            Qty                        types
IEC type                    provided                   supported
 
IEC-320-C13                 8                          --
 (10A)
IEC-320-C19                 4                          --
 (16A)
IEC309 (P+N+G)              1                          46
 (32A)

If the plug type selected for the equipment to be protected by the 9910-P64 is not contained in this table, use the output power cables contained in feature number 9830.

A summary of output power cords included with the 9910-P64 and feature number 6572 configuration is contained in the following table:

9910-P64 with feature 6572 and two feature 9830 output power cord table

                   Receptacle
Plug type          type               Length            Quantity
 
IEC-320-C14        IEC-320-C13        6 ft/1.8m         8
IEC-320-C20        IEC-320-C19        14 ft/4.4m        4

Power electrical cable installation diagrams are located at the following Web sites:

NEMA countries

IEC countries

Feature 6641 (External Battery Module)

The input power to the 6641 is DC and is provided by the P64. Connection of the 6641 DC cable (Anderson-type DC connector) is the responsibility of the client and is performed at installation. Feature number 6641 is a line-up-and-match cabinet connected to P64 cabinet.

Communications cables

One server to UPS serial TTY interface cable DB9M to DB9F (6 ft/1.8 m length) is included with the P64 (contained in the P64 Accessory Kit carton (IBM part number 38P9309)) for all (iSeries and pSeries) orders. The P64 includes a single serial port (DB9) and a USB port, both are contained on the backplane of the device. An empty ConnectUPS X-Slot interface port is available for optional communications features (#2933, #2934, and #2936). Communications is employed in an "or" configuration: serial or USB or ConnectUPS card. A maximum of one feature number 2933, or 2934, or 2936 is supported.

The optional feature number 2933 (ConnectUPS MultiServer Card) includes three server to UPS serial TTY interface cables DB9 to DB9 (6 ft/1.8 m length). Min: 0, Max: 1 per P64.

Note: This feature number is used to serially communicate with two or three servers.

The optional feature number 2934 (ConnectUPS Web/SNMP/xHub Card) includes one UPS to Web Card configuration cable RJ45 to DB9M (6 ft/1.8 m length).

Note: This is required if using LPAR on pSeries. Min: 0, Max: 1 per P64.

The optional feature number 2936 (ConnectUPS Relay Card) includes one iSeries (AS/400) to UPS interface cable (25 ft/7.6 m length). This feature number is included with iSeries orders. Min: 0, Max: 1 per P64.

The optional feature number 2938 (ConnectUPS EMP) includes one CAT5 cable (6 ft/1.8 m length). Corequisite is feature number 2934. Min: 0, Max: 1 feature number 2938 per feature number 2934.

Security, auditability, and control

The customer is responsible for evaluation, selection, and implementation of security features, administrative procedures, and appropriate controls in application systems and communications facilities.
 
Back to top
 

Terms and conditions

This product is available for purchase under the terms of the IBM Customer Agreement.

Each IBM Machine is manufactured from parts that may be new or used. In some cases, a Machine may not be new and may have been previously installed.

Regardless, IBM's appropriate warranty terms apply.

IBM Global Financing: No

Warranty period: This product is available for purchase under the terms of the IBM Customer Agreement.

IBM hardware products are manufactured from new parts, or new and used parts. In some cases, the hardware product may have been previously installed. Regardless, IBM warranty terms apply.

Models P30 and P64 have a five-year Advanced Element Exchange Warranty (including battery) provided by Powerware with IBM as point of contact.

Model P93 has a five-year, on-site, Next-Business-Day (NBD) Warranty provided by Powerware with IBM as point of contact.

When a type of service involves the exchange of a machine part, the replacement may not be new, but will be considered equivalent to new.

Warranty Service

IBM 9910 UPS Models P30 and P64 provide a premium Element Exchange Warranty. In case of problems with the UPS, contact IBM Service Support. IBM will coordinate remote diagnostics and manage the Element Exchange Warranty, if necessary.

If a replacement element is required, the UPS manufacturer will process and ship the request the same day if the request is received before noon (12:00 p.m.) local time. After noon, the replacement element will be shipped the following business day. The replacement element will be next-day air service (same type of carrier used in the U.S., for example, Federal Express, Airborne Express). The shipping costs to and from the client location are the responsibility of the UPS manufacture.

Advanced Element Exchange Warranties DO NOT include on-site service unless specifically noted in writing at the time of equipment sale.

IBM 9910 Models P93 and P95 provide on-site, NBD service. In case of problems with the UPS, contact IBM Service Support. IBM will coordinate having a Powerware Service representative on site to perform diagnostics and repair action if necessary.

A Powerware Service Representative will arrive the next business day (P95 most countries) when the service request is placed before noon local time. If the service request is received after noon local time, the Powerware representative will be on site the second business day after the service request was placed.

In addition, Powerware offers optional ProActive Warranty Service Plans feature number 7001 concurrent (one additional year) or feature number 7002 non-concurrent (one additional year). The ProActive service plan includes:

  • 24x7 corrective maintenance coverage.
  • 24x7 annual performance check.
  • Annual power protection audit.
  • 24x7 remote monitoring advance response service5.
  • Monthly UPS performance report5.
  • Web access to account information and site service activity.
  • Feature number 7001: One additional year of ProActive Warranty Service Plan. Concurrent to purchase of P93. Min: 0, Max: 4. Must be purchased at the same time the P93 is ordered.
  • Feature number 7002: One additional year of ProActive Warranty Service Plan. Non-concurrent to purchase of P93. Min: 0, Max: 4.
5
Requires use of P93 modem and client-provided dedicated analog (outside) phone line.

Note: One year of ProActive Warranty Service is included in the purchase price of the P93.

Client responsibility

For 9910 Models P30 and P64, the clients' responsibilities for element exchange are:

  • Receipt, unpacking, and exchange of the defective element.
  • Packaging of the defective element in the container received with the replacement element.
  • Following the instructions provided for return of the defective element. Returning the defective element so that it is received at Powerware UPS Systems depot center within the established time from the arrival of the replacement.

For 9910 Models P93 and P95, the client will be contacted to coordinate the on-site service provided by Powerware. Powerware maintains a 24-hour hotline for technical support at 800-925-4426 in the U.S. and Canada, or +1 919-870-3149. Contact the local Powerware agent for all other countries.

Technical information can also be accessed at the following Web site

Warranty service is available from IBM Field Support Services Center at 800-IBM-SERV (426-4968).

Usage plan machine: No

IBM hourly service rate classification: Two

These machines are not under the IBM Maintenance Agreement. Contact your local IBM Services Branch office for Post Warranty Options.

When a type of service involves the exchange of a machine part, the replacement may not be new, but will be in good working order.

Field-installable features: Yes

Model conversions: No

Machine installation: Customer Setup, customers are responsible for installation according to the instructions IBM provides with the Machine.

Graduated charges: No. These products do not contain Licensed Internal Code or Licensed Machine Code.

Educational allowance: A reduced charge is available to qualified education customers. The educational allowance may not be added to any other discount or allowance.

Educational Allowance

A reduced charge is available to qualified education clients. The educational allowance may not be added to any other discount or allowance.

The educational allowance is 15% for the products in this announcement.
 
Back to top
 

Prices

The prices provided in this announcement are suggested retail prices for the U.S. only and are provided for your information only. Dealer prices may vary, and prices may also vary by country. Prices are subject to change without notice. For additional information and current prices, contact your local IBM representative.

Product charges

UPS

                                   Machine         Feature
Description                        type    Model   number  Price  CSU
 
Powerware 9125 3 kVA tower or      9910    P30            $ 3,082 Yes
 rack-mount
Powerware 9125 3 kVA Battery       9910    P30     6640       783 Yes
 Module
Powerware 9125 3 kVA tower PPDM    9910    P30     6570       858 Yes
 (NEMA dist. module)
Powerware 9125 6 kVA tower or      9910    P64              4,411 Yes
 rack-mount
Powerware 9125 6 kVA Battery       9910    P64     6641       990 Yes
 Module
Powerware Rail Kit A               9910    P64     6631       150 Yes
Powerware 9125 6 kVA tower PPDM    9910    P64     6571       773 Yes
 (NEMA dist. module)
Powerware 9125 6 kVA tower PPDM    9910    P64     6572       773 Yes
 (IEC dist. module)
Powerware X-Slot Relay Card/Cable  9910    P30/P64 2936       153 Yes
                                           P33
Powerware jumper cord kit          9910    P30/P64 9830       120 Yes
 (IEC plugs) for iSeries Rack              P33
 P30 tower w/o PPDM
P64 tower with IEC PPDM (2 sets)
Powerware Environmental Probe      9910    All     2938       164 Yes
 for 2934 and 2935
Power Cord L6-30 to L6-30 6 ft     9910    P64     2970        67 Yes
 PDU to UPS
Power Cord/Redundant Power Source  9910    P30/P33 9874        39 Yes
 IBM Plug Type 54 14 ft
Power Cord/Redundant Power Source  9910    P30/P33 9875        47 Yes
 IBM Plug Type 64 14 ft
Power Cord/Redundant Power Source  9910    P30/P33 9860        44 Yes
 IBM Plug Type 11 14 ft
Power Cord/Redundant Power Source  9910    P30/P33 9861        42 Yes
 IBM Plug Type 11 6 ft
Power Cord L6-30 to L6-30 14 ft    9910    P64     1420        82 Yes
Power Cord L6-30 to L6-30  6 ft    9910    P64     1421        67 Yes
Power Cord L6-30 to Russellstoll   9910    P64     1422       141 Yes
 6 ft
Power Cord L6-30 to Russellstoll   9910    P64     1423       154 Yes
 14 ft
Power Cord L6-30 to Korea 30A      9910    P64     1425        97 Yes
Power Cord L6-30 to Australia 30A  9910    P64     1426       202 Yes
 (PDL)
Power Cord L6-30 to New Zealand    9910    P64     1427       202 Yes
 
 30A (PDL)
Factory Installation of MT 9910 in 9910    P30/P64 9012        NC NA
 iSeries rack                              P33
Field Installation of MT 9910 in   9910    P30/P64 9013        NC NA
 iSeries rack
Tower Form Factor                  9910    P30/P64 9014        NC NA
Rack Cont. Specify: 9910/P30-2EIA  7014    T00/T42 0243        NC NA
 (UPS, 6 C13 Outlets)
Rack Cont. Specify: 9910/6640-2EIA 7014    T00/T42 0244        NC NA
 (9910-P30 Battery Module)
Rack Cont. Specify: 9910/P64-5EIA  7014    T00/T42 0245        NC NA
 (UPS, 6 C13 Outlets)
 
                                   Machine         Feature
Description                        type    Model   number  Price  CSU
 
Rack Cont. Specify: 9910/6641-3EIA 7014    T00/T42 0246        NC NA
 (9910-P64 Battery Module)
Powerware 9330-20 20 kVA           9910    P93            $38,345 No
Powerware Extended Battery Module  9910    P93     6635     7,311 No
 (EBM) for P93
IBM IPR Site Survey                9910    P93     7005       360 No
ProActive Warranty Service Plan    9910    P93     7001     1,596 No
 Concurrent (One additional year)
ProActive Warranty Service Plan    9910    P93     7002     2,272 No
 Non-Concurrent
 (One additional year)
Output Connections, two IEC 60A    9910    P93     9880     2,617 No
Output Connections, three NEMA 15A 9910    P93     9881     2,084 No
 to 30A

NC = No Charge
NA = Not Applicable
CSU = Customer Set-Up

Field          Plant                       MES            MES
install        install       MES           removal        add
only           only          removal       charge         charge
 
N              N             N             NC             NC

 
Back to top
 
Order now

To order, contact the Americas Call Centers, your local IBM representative, or your IBM Business Partner.

To identify your local IBM representative or IBM Business Partner, call 800-IBM-4YOU (426-4968).

 Phone:     800-IBM-CALL (426-2255)
 Fax:       800-2IBM-FAX (242-6329)
 Internet:  ibm_direct@vnet.ibm.com
 Mail:      IBM Americas Call Centers
            Dept:  IBM CALL, 6th Floor
            105 Moatfield Drive
            North York, Ontario
            Canada M3B 3R1
 
 Reference: YE001

The Americas Call Centers, our national direct marketing organization, can add your name to the mailing list for catalogs of IBM products.

Note: Shipments will begin after the planned availability date.

Trademarks

 
iSeries is a trademark of International Business Machines Corporation in the United States or other countries or both.
 
pSeries, the e-business logo, OS/400, AIX, PowerPC, AS/400, and SAA are registered trademarks of International Business Machines Corporation in the United States or other countries or both.
 
Intel is a trademark of Intel Corporation.
 
Other company, product, and service names may be trademarks or service marks of others.

Back to top
 

 
Printable version